Chateau™ Decorative Gas Appliance
20009543
Sealing firestop gaps with high temperature sealant 
will restrict cold air being drawn in around fire-
place.
STEP 8
Guide the vent terminations 8” and 11” collars into their 
respective vent pipes. Double check that the vent pipes 
overlap the collars by 2” (51 mm). Secure the termina-
tion to the wall with screws provided and caulk around 
the wall plate to weatherproof. (Fig. 24) As an alterna-
tive to screwing the termination directly to the wall you 
may also use expanding plugs or an approved exterior 
construction adhesive.
FP1458
Fig. 23  Through the wall.
FP1457
Fig. 22  Horizontal length requirement.
X
FP1460
Fig. 24   Secure termination to wall.
Support horizontal pipes every 3’ (914 mm) 
with metal pipe straps.                         
Check fireplace to make sure it is levelled 
and properly positioned.
Sidewall Installation with 
Stationary Glass Facing Outside
CAUTION: Unit must be installed with stationary 
glass facing outside. (Control panel assembly will 
be located on the left side of the unit when facing 
the unit form inside house.) 
Failure to do so will result in a major reconstruction 
and CFM Corporation will not be responsible for 
costs associated with incorrect installation.
CAUTION: Control panel assembly must be 
installed on the inside of the house and not 
on the outside.
STEP 1
Locate vent opening on the wall. It may be necessary 
to first position the fireplace and measure to obtain hole 
location. Depending on whether the wall is combustible 
or noncombustible, cut opening to size. (Fig. 19)
For combustible walls first frame in opening.
Combustible Walls: Cut a 16¹⁄₄”H x 16¹⁄₄” W (413 x 413 
mm) hole through the exterior wall and frame as shown.
Noncombustible Walls: Hole opening must be 11¹⁄₄” 
(286mm) in diameter. 
STEP 2
Measure wall thickness and cut zero clearance sleeve 
parts to proper length (MAXIMUM 12”/305 mm). As-
semble sleeve using #8 sheet metal screws (supplied). 
(Fig. 20) Install firestop assembly. (Fig. 30)