Monessen Hearth MJ27NR 用户手册

下载
页码 40
86D0024
15
FP2002
mantel clearances unsafe
2
1
/
2
"
8"
6"
7"
14
1
/
2
"
4"
Mantel
Minimum 
of 8" Heat 
Resistant 
Material
Hood
FP2002
Figure 9 - Minimum Mantel Clearance with Hood - MJ27
(Example of Unsafe Installation) 
CLEARANCES and HEIGHT REQUIREMENTS
Figure 9 is an example of an unsafe mantel instal-
lation. This mantel projects 4" at 8" above the opening, 
exceeding  the  maximum  acceptable  distance  of  2
1
/
2
The mantel also projects 7" at 14
1
/
2
" above the opening, 
exceeding the maximum acceptable distance of 6".
If your mantel profile is unsafe, you may either:
  • Raise the mantel to an acceptable height 
  OR
  • Remove the mantel