Quadra-Fire  •  QVI30S, QVI35S  •  340-901 Rev. F  • 7/08  
6
TOP VIEW
A
C
B
Fireplace Size Requirements 
 
Figure 3.1  Fireplace Opening
NOTE:  For actual appliance dimensions refer to Section 16.
Fire Risk
Provide adequate clearance:
•  Around air openings
• To combustibles
•  For service access
Locate appliance away from traffi c areas.
WARNING
Minimum Appliance Size   
Location
QVI35S
QVI30S
Inches
Millimeters Inches
Millimeters
A
  Front Width  33-1/4
845
29-1/4
743
B
  Rear Width   24-1/4
616
20-1/4
515
C
  Depth 
13-5/8
346
13-5/8
346
*
  Height
22-3/4
578
20-1/4
515
* NOTE: If exhaust collar on insert and fi replace damper do not line up, add 4 
inches (102mm) to minimum fi replace height for bends in vent pipe.
A.  Minimum Fireplace Opening
Minimum  fi replace opening requirements are shown in 
Figure 3.1. 
• The fi rebrick (refractory), glass doors, screen rails, 
screen mesh and log grates can be removed from a 
factory built fi rebox in order to gain minimum gas insert 
opening requirements.
•  Any smoke shelves, shields, baffl es and the metal fl oor 
of the unit may be removed from a factory built fi rebox if 
attached with mechanical fasteners. If the appliance is 
placed on the base of the outer wrap, a ¼ inch airspace 
must be provided between the insert and the fl oor of the 
outer wrap.
•  Cutting of any sheet metal parts of the fi replace in which 
the gas fi replace insert is to be installed is prohibited.