BEFORE INSTALLATION
The controller is available in three models (see Table 1).
Review the power, input, and output specifications on page 2 
before installing the controller.
— Hardware driven by Triac outputs must have a minimum 
current draw, when energized, of 25 mA and a maximum 
current draw of 500 mA.
— Hardware driven by the analog current outputs must have a 
maximum resistance of 550 Ohms, resulting in a maximum 
voltage of 11 volts when driven at 20 mA.
If resistance exceeds 550 Ohms, voltages up to 18 Vdc are 
possible at the analog output terminal.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring or 
making wiring connections to prevent electrical shock 
or equipment damage.
INSTALLATION
The controller must be mounted in a position that allows 
clearance for wiring, servicing, removal, connection of the 
BACnet MS/TP Molex connector and access to the MS/TP 
MAC address DIP switches (see Fig. 15 on page 12).
The controller may be mounted in any orientation.
IMPORTANT
Avoid mounting in areas where acid fumes or other 
deteriorating vapors can attack the metal parts of the 
controller, or in areas where escaping gas or other 
explosive vapors are present. Fig. 6–Fig. 7 on page 5 
for mounting dimensions.
For the PVB6436AS model, the actuator is mounted first and 
then the controller is mounted. For the other models, go to 
“Mount Controller” on page 5 to begin the installation.
Mount Actuator onto Damper Shaft 
(PVB0000AS, PVB4022AS and 
PVB6436AS)
PVB0000AS, PVB4022AS and PVB6436AS controllers include 
the direct-coupled actuator with Declutch mechanism, which is 
shipped hard-wired to the controller.
The actuator mounts directly onto the VAV box damper shaft 
and has up to 44 lb-in. (5 Nm) torque, 90-degree stroke, and 90 
second timing at 60 Hz. The actuator is suitable for mounting 
onto a 3/8 to 1/2 in. (10 to 13 mm) square or round VAV box 
damper shaft. The minimum VAV box damper shaft length is 1-
9/16 in. (40 mm).
The two mechanical end-limit set screws control the amount of 
rotation from 12° to 95°. These set screws must be securely 
fastened in place. To ensure tight closing of the damper, the 
shaft adapter has a total rotation stroke of 95° (see Fig. 1).
NOTES:
1.
The actuator is shipped with the mechanical end-
limit set screws set to 95 degrees of rotation. 
Adjust the two set screws closer together to 
reduce the rotation travel. Each “hash mark” indi-
cator on the bracket represents approximately 6.5° 
of rotation per side.
2.
The Declutch button, when pressed, allows you to 
rotate the universal shaft adapter (see Fig. 1).
IMPORTANT
Determine the damper rotation and opening angle 
prior to installation. See Fig. 2 below and Fig. 3 on 
page 4 for examples.
 
Fig. 1. Series 60 Floating Actuator.
TR23
Setpoint
Potentiometer
500 Ohm
to
10,500 Ohm
-4° DDC to +4° DDC
(-8° DDF to +7° DDF)
or
50 F to 90 F 
(10 C to 32 C)
Resistive Input Generic
100 Ohms to 100K Ohms
Voltage
Input
Transducer,
Controller
0–10 Vdc
Discrete Input Dry Contact 
closure
Open Circuit > 3000 Ohms
Closed Circuit < 3000 Ohms
a
C7031G and C7041F are recommended for use with these 
controllers, due to improved resolution and accuracy when 
compared to the PT1000.
Input
Type
Sensor
Type
Operating
Range
UNIVERSAL SHAFT
CLAMPING BOLTS (2)
M23568
UNIVERSAL
SHAFT ADAPTER
MECHANICAL
END LIMIT SET
SCREWS (2)
DECLUTCH
BUTTON