Mitsumi electronic 13JX10 Benutzerhandbuch
2 SPECIFICATIONS
2.1 Performance Specifications
17
2
2
SPECIFICATIONS
This chapter describes the specifications of the master/local module.
2.1
Performance Specifications
This section describes the performance specifications of the master/local module.
Item
Description
Transmission speed
Selected from 156kbps, 625kbps, 2.5Mbps, 5Mbps, and 10Mbps.
Maximum number of connectable
modules (master station)
modules (master station)
64
Number of occupied stations (local
station)
station)
1 to 4 stations (The number of stations can be changed using the engineering tool.)
Maximum number
of link points per
system
of link points per
system
CC-Link Ver.1
• Remote I/O (RX, RY): 2048 points
• Remote register (RWw): 256 points (master station
• Remote register (RWw): 256 points (master station
remote device station/local station/intelligent device
station/standby master station)
• Remote register (RWr): 256 points (remote device station/local station/intelligent device station/standby master
station
master station)
CC-Link Ver.2
• Remote I/O (RX, RY): 8192 points
• Remote register (RWw): 2048 points (master station
• Remote register (RWw): 2048 points (master station
remote device station/local station/intelligent device
station/standby master station)
• Remote register (RWr): 2048 points (remote device station/local station/intelligent device station/standby master
station
master station)
Number of link points per remote station/
local station/intelligent device station/
standby master station
local station/intelligent device station/
standby master station
Communication method
Broadcast polling method
Synchronization method
Frame synchronization method
Encoding method
NRZI method
Network topology
Bus (RS-485)
Transmission format
HDLC compliant
Error control system
CRC (X
16
+ X
12
+ X
5
+ 1)
Connection cable
Ver.1.10-compatible CC-Link dedicated cable
Maximum overall cable length (maximum
transmission distance)
transmission distance)
Depends on the transmission speed ( Page 22 Maximum Overall Cable Length)
RAS function
• Standby master station
• Automatic return function
• Slave station cutoff function
• Error detection using link special relay areas (SB) and link special register areas (SW)
• Automatic return function
• Slave station cutoff function
• Error detection using link special relay areas (SB) and link special register areas (SW)
Number of occupied I/O points
32 points
Internal current consumption (5VDC)
0.34A
Weight
0.16kg