Honeywell DCP200 Benutzerhandbuch

Seite von 184
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Electrical Installation
Page 29
Option Slot 1 Connections
Option Slot 1 – Single Relay Output Module
If option slot 1 is fitted with a single relay output module, make connections as illustrated. 
The relay contacts are SPDT and rated at 2 amps resistive, 240 VAC.
Figure 14.
Option Slot 1 – Single Relay Module
Option Slot 1 – Single SSR Driver Output Module
If option slot 1 is fitted with a single SSR driver output module, make connections as 
illustrated. The solid-state relay driver is a 0-10V DC signal, load impedance must be no less 
than 500 ohms. SSR driver outputs are not isolated from the signal input or other SSR driver 
outputs.
Figure 15.
Option Slot 1 – Single SSR Driver Module
Option Slot 1 - Triac Output Module
If option slot 1 is fitted with a Triac output module, make connections as shown. This output 
is rated at 0.01 to 1 amp @ 280V AC 50/60Hz. A snubber should be fitted across inductive 
loads to ensure reliable switch off the Triac.
Figure 16.
Option Slot 1 - Triac Module
19
20
N/C
COM
21
N/O
19
20
_
21
+
20
21
