SITRANS LR 460 – INSTRUCTION MANUAL
Page 49
mmmmm
Pa
ra
ra
m
e
te
rs
PROFIBUS Ident Number (PROFIBUS PA devices only)
Identifies the device on the network. The Ident Number must match that in the
GSD file (the GSD file provides information on the device to the master).
Last config
Date on which the device was installed. The user must enter the date.
Local Operation Enable
Enables/disables programming the device via the handheld programmer. When
disabled, the user still has access to the mode control of the two Analog Input
Function Blocks.
2.2.4. Write Locking
Prevents any changes to parameters via PDM or the handheld programmer.
Open the menu Device – Write Locking, and select On or Off.
2.2.5. Language
Selects the language to be used on the LCD.
2.3. Statistics
To view Statistics via PDM, open the menu View – Wear.
2.3.1. Powered
Hours
Number of hours the unit has been powered up since manufacture.
2.3.2. Power-on Resets
The number of power cycles that have occurred since manufacture.
Values
0
Profile-specific (uses generic device DD and profile GSD for
class B device)
class B device)
1
Manufacturer-specific (uses Siemens Milltronics DD and
GSD file, which identifies the LR 460.
GSD file, which identifies the LR 460.
Options
UNLOCKED
*
programming enabled
LOCKED
programming disabled
Options
*
English
German
French
Spanish
German
French
Spanish