SPX Cooling Technologies TG MAG86-100 Benutzerhandbuch

Seite von 72
9
A.0500.551 – IM-TGMAG/02.00 EN (02/2008)
1.3.2   Pump units
1.3.2.1  Pump unit handling
Use an overhead crane, forklift or other suitable lifting device.
Secure lifting slings around the front 
part of the pump and the back part of 
the motor. Make sure that the load is 
balanced before attempting the lift. 
NB! Always use two lifting slings.
If there are lifting rings on both the 
pump and the motor the slings may be 
fastened to these. 
NB! Always use two lifting slings.
Warning
Never lift the pump unit with only one 
fastening point. Incorrect lifts can re-
sult in personal injury and/or damage 
to the unit.
1.3.2.2  Installation
All pump units should be equipped with a locking safety switch to prevent accidental start during 
installation, maintenance or other work on the unit.
Personnel who have a pacemaker should not be allowed to work with the magnetic 
coupling!  
The magnetic field is sufficiently strong to affect the operation of a pacemaker. A safe 
distance is 3 metre!
Always keep electronic equipment with memory, cheque cards with magnetic strips, 
and similar items at least 1 metre away from the coupling!
Warning 
The safety switch must be turned to off and locked before any work is carried out on the pump unit. 
Accidental start can cause serious personal injury.
The pump unit must be mounted on a level surface and either be bolted to the foundation or be fitted 
with rubber-clad feet.
The pipe connections to the pump must be stress-free mounted, securely fastened to the pump and 
well supported. Incorrectly fitted pipe can damage the pump and the system.
Warning 
Electric motors must be installed by authorized personnel in accordance with EN60204-1. Faulty 
electrical installation can cause the pump unit and system to be electrified, which can lead to fatal 
injuries.
Electric motors must be supplied with adequate cooling ventilation. Electric motors must not be 
enclosed in airtight cabinets, hoods etc.
Dust, liquids and gases which can cause overheating and fire must be diverted away from the  
motor.
Warning 
Pump units to be installed in potentially explosive environments must be fitted with an Ex-class 
(explosion safe) motor. Sparks caused by static electricity can give shocks and ignite explosions. 
Make sure that the pump and system are properly grounded. Check with the proper authorities for 
the existing regulations. A faulty installation can lead to fatal injuries.