Honeywell MRP-2001E Benutzerhandbuch

Seite von 136
Template 11: Single Hazard - 3 Zones and Low Pressure
FACP Configuration Templates
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
113
B.5  Template 11: Single Hazard - 3 Zones and Low Pressure 
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding 
output circuit).
Input Zone Types: 
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow  - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Zone 4 = Manual Release
Zone 5 = Pull Station
Zone 6 = Low Pressure
Output Circuit Types:
Output 1 = Alarm NAC
Output 2 = Waterflow NAC - activation delayed for 10 secs. (Waterflow Delay set to10 secs.)
Output 3 = Supervisory Bell NAC
Output 4 = Release Solenoid 1 (unsupervised for shorts)
Timers
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 10 seconds
AC Loss Delay Timer - set for 2 hours
Operation
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or 
Zone 5 (Pull Station) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output 
#4.  Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak 
Timer 1
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2.  There is 
a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10 
seconds
Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation. 
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3 
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull 
Station) will operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
TEMPLATE 11: SINGLE HAZARD - 3 ZONES AND LOW PRESSURE
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE SMOKE
FIRE
WATERFLOW
MANUAL 
RELEASE
PULL 
STATION
LOW 
PRESS.
#1 ALARM NAC
X
X
X
X
#2 WATERFLOW NAC
X
#3 SUPV. BELL NAC
X
#4 RELEASE SOLENOID 1
X
X
X
X