Product Description
Controls and Indicators
14
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA (see note 1)
Power-limited Circuitry
Jumper selectable by JP31 for resettable or nonresettable power:
 Jumper pins 1 & 2 on JP31 for nonresettable power
 Jumper pins 2 & 3 on JP31 for resettable power
Refer to the Device Compatibility Document for compatible listed devices
1.3 Controls and Indicators
LCD Display         
The FACP uses an 80-character 
(4 lines X 20 characters) high viewing angle 
LCD display.  The display includes a long life 
LED backlight that remains illuminated.  If AC 
power is lost and the system is not in alarm, the 
LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and 
indicators as listed above.  The key panel, which is visible with the cabinet door closed, has 25 
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silence
Drill
System Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
 
 SYSTEM ALL NORMAL
 10:00A 012106
Figure 1.1 Membrane/Display Panel
MRP
2001kypd.c
dr