Honeywell MRP-2001E Benutzerhandbuch

Seite von 136
Installation of Optional Modules
Installation
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
27
2.6.1.2 Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB5 of the FACP main circuit 
board and TB2 of the CAC-5X module.  Wire the Style D (Class A) Initiating Device Circuits 
using TB4 of the FACP main circuit board and TB1 of the CAC-5X.  Note that the wiring will 
be identical when using TB7 NAC and TB6 IDC of the FACP.  Make certain to observe polarity 
when connecting the devices to the circuits.  The B+ and A+ terminals must comprise the feed 
and return for the positive side of a device and the B- and A- terminals must comprise the feed 
and return for the negative side of a device.  To configure any of the zones for Class B when the 
CAC-5X is installed, simply wire to the B+ and B- input on the FACP terminal(s) and install the 
End-of-Line Resistor after the last device on the circuit.  Do not wire to the corresponding A+ 
and A- terminals on the CAC-5X module.
Figure 2.12 Wiring NACs and IDCs for Class A Operation
CAC-5X Class A Converter Module
FACP Main
Circuit Board
Class B (Style B) IDC - 4.7 K
Ω
½ watt ELR resistor
P/N:71252 (supervised and power-limited)
Dummy load all unused 
circuits - 4.7 K
Ω
½ watt ELR resistor 
(P/N: 71245)
Polarized
Bell
Circuit polarities 
shown in alarm 
condition
Class A (Style Z) NAC 
(supervised and power-limited)
Class A (Style D) IDC
 (supervised and power-limited)
Polarized
Strobe
Polarized
Horn
Smoke
Smoke
Pull Station
Pull Station
Heat
Heat
ms
10udc
la
ssa.cdr
B+     B-
B+     B-
A+     A-
A+     A-
A+    A-  A+  A-   A+   A-   A+   A-   A+   A-
B+   B-   B+   B-   B+   B-   B+   B-   B+   B-
Ferrite Bead
P/N 29150
Large gauge wire should be looped through 
bead at least once as illustrated.  Smaller 
gauge wire can be looped more often.
Ferrite Bead in open position
Ferrite Bead in closed position
2550f
err
.cdr