ANN-BUS Devices
Installation
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
33
2.7.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply
Figure 2.16 illustrates the powering of ANN-BUS devices from an auxiliary power supply such 
as the FCPS-24FS6/8, when the maximum number of ANN-BUS devices exceeds the ANN-
BUS power requirements. 
2.7.2 ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the 
FACP.  A 5-position DIP switch on each device is used to set this address.  The address set for these 
devices must also be programmed at the FACP for the specific device (refer to the programming 
section titled  "ANN-BUS" on page 71).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit.  Device 
addresses do not need to be sequential and can be set to any number between 01 and 08.  Note that 
00 is not a valid address.  The following table shows the DIP switch setting for each address. 
Note: address (ID Number) DIP switches on some devices may have more than 5 switch positions.  
Unless otherwise specified in the documentation supplied with each device, switch positions 6 and 
above must be set to OFF.
 
Address
Switch 5
Switch 4
Switch 3
Switch 2
Switch 1
not valid
OFF
OFF
OFF
OFF
OFF
01
OFF
OFF
OFF
OFF
ON
02
OFF
OFF
OFF
ON
OFF
03
OFF
OFF
OFF
ON
ON
04
OFF
OFF
ON
OFF
OFF
05
OFF
OFF
ON
OFF
ON
06
OFF
OFF
ON
ON
OFF
07
OFF
OFF
ON
ON
ON
08
OFF
ON
OFF
OFF
OFF
Figure 2.16 Powering ANN-BUS Devices from FCPS-24FS6/8
ANN-80
FACP
FCPS-24FS6/8
+24 VDC
-24 VDC
ANN-BUS
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
ANN-BUS and power wiring are 
supervised and power-limited
TB3
a
nn80t
oFCP
Srp2001.cdr