Honeywell MRP-2001E Benutzerhandbuch

Seite von 136
Installation
ANN-BUS Devices
38
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
2.7.6.2.1 Connecting PRN-6 Printer
Remote printers require a primary AC power source.  If required for the fire alarm system 
configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a 
secondary power source (battery backup).  Since a secondary power source is not provided as a 
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used.  
The building emergency power supply may be used, as long as it meets the power continuity 
requirements of NFPA 72.  Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 
cable.  One end of the cable will plug into the DB-25 connector on the PRN printer and the 
other end plugs into the parallel connector on the ANN-S/PG module.  Note that the 9-pin DB-
9 port on the ANN-S/PG is used to connect a serial printer.  The 25-pin port is used for a 
Centronics parallel printer cable.  Connect either a serial or parallel printer, but not both at the 
same time.
2.7.6.2.2 Setting Printer Options
Refer to the documentation supplied with the PRN printer for instructions on using the printer 
menu controls.  Set the printer options (under the menu area) as shown in the following table: 
Table 2.2  PRN-6 Setup Options
Option
Setting
Option
Setting
Font
HS Draft
CPI
10CPI
LPI
6 LPI
Skip
0.5
ESC Character
ESC
Emulate
Epson FX-850
Bidirectional Copy
ON
I/O
CG-TAB
Graphic
    Buffer
40K
Country
E-US ASCII
Serial
Auto CR
OFF
    Baud
9600 or 2400
Color Option
Not Installed
    Format
7 Bit, Even, 1 Stop
Formien
    Protocol
XON/XOFF
    Lines
6LPI=60
Character Set
Standard
    Standard
Exec 10.5
SI.Zero
On
Auto LF
On
PAPER
    BIN 1
12/72”
    BIN 2
12/72”
    SINGLE
12/72”
    PUSH TRA
12/72”
    PULL TRA
12/72”
    PAP ROLL
12/72”