Honeywell MRP-2001E Benutzerhandbuch

Seite von 136
Master Programming Level
Programming
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
73
3.5.7.3 Auto-Configure
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed 
ANN-BUS modules online.  The software will search for all ANN-BUS modules and 
automatically program the device type and address into the system.  Pressing 3 while viewing 
ANN-BUS Screen #1 will begin the Auto-Configure process and cause the following screen to 
be displayed: 
3.5.7.4 ANN-S/PG Options
The Printer Option allows the user to configure the optional printer.  Pressing 1 while viewing 
the ANN-BUS Screen #2 will display the following screens: 
Pressing 1 for Port while viewing Printer Options screen #1 will allow the programmer to select 
between a Parallel and Serial Port for printer connection.  Each press of the 1 key will cause the 
display to toggle between Port PAR (parallel) and Port SER (serial).  It is important to note that 
the interface selected determines which options are available to the user.
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen  
  PROGRAMMING
1=ANN-S/PG OPTIONS
2=ANN-I/O OPTIONS
3=ANN-80 OPTIONS
ANN-BUS Screen #2
  ANN-S/PG OPTIONS
1=PORT        PARALLEL
2=PRINTER SUPV      NO
3=OFFLINE TIMER     60
Printer Options Screen #1  
  ANN-S/PG OPTIONS
1=BAUD RATE      N/A
2=DATA BITS      N/A
3=PARITY         N/A
Printer Options Screen #2  
  ANN-S/PG OPTIONS
1=STOP BITS      N/A
Printer Options Screen #3