Honeywell MRP-2001E Benutzerhandbuch
Master Programming Level
Programming
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
77
3.5.7.7 ANN-RLY Options
Pressing 1 for ANN-RLY Options while viewing ANN-BUS Screen #3 will cause the following
screen to be displayed:
Pressing 1 for ANN-RLY Options while viewing ANN-BUS Screen #3 will cause the following
screen to be displayed:
The ANN-RLY module provides ten Form-C relays which can be programmed for various
functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will
display the remaining relays for this module.
functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will
display the remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option
screen, press the number key corresponding to the relay to be programmed. Following is a list
of the available programming options for each relay:
screen, press the number key corresponding to the relay to be programmed. Following is a list
of the available programming options for each relay:
•
General Alarm
•
General Trouble
•
General Supervisory
•
Future Use
•
Future Use
•
Future Use
•
General Discharge
•
Discharge Release 1
•
Discharge Release 2
•
AC Loss
•
Waterflow Delay
•
Future Use
•
Future Use
•
Future Use
•
General 2nd Shot Release
•
2nd Shot Release 1
•
2nd Shot Release 2
•
Input Zone 1
•
Input Zone 2
•
Input Zone 3
•
Input Zone 4
•
Input Zone 5
•
Input Zone 6
PROGRAMMING
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3
ANN-RLY OPTIONS
1=RELAY 1 IN ZONE 1
2=RELAY 2 IN ZONE 2
3=RELAY 3 IN ZONE 3
1=RELAY 1 IN ZONE 1
2=RELAY 2 IN ZONE 2
3=RELAY 3 IN ZONE 3
ANN-RLY Options Screen