Honeywell MRP-2001E Benutzerhandbuch

Seite von 136
Master Programming Level
Programming
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
77
3.5.7.7 ANN-RLY Options
Pressing 1 for ANN-RLY Options while viewing ANN-BUS Screen #3 will cause the following 
screen to be displayed:
The ANN-RLY module provides ten Form-C relays which can be programmed for various 
functions.  The initial screen displays Relays 1 through 3.  Pressing the down arrow key will 
display the remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option 
screen, press the number key corresponding to the relay to be programmed.  Following is a list 
of the available programming options for each relay:
General Alarm
General Trouble
General Supervisory
Future Use
Future Use
Future Use
General Discharge
Discharge Release 1
Discharge Release 2
AC  Loss
Waterflow Delay
Future Use
Future Use
Future Use
General 2nd Shot Release
2nd Shot Release 1
2nd Shot Release 2
Input Zone 1
Input Zone 2
Input Zone 3
Input Zone 4
Input Zone 5
Input Zone 6
  PROGRAMMING
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3
  ANN-RLY OPTIONS
1=RELAY 1   IN ZONE 1
2=RELAY 2   IN ZONE 2
3=RELAY 3   IN ZONE 3
ANN-RLY Options Screen