CONFIGURABLE ZONE TYPES WORKSHEETS  
 
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data 
fields*182-*185. Configurable zone types 92 and 93 (FA168CPS only) can only be programmed using the 
downloader software. 
 
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and 
field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the 
tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types. 
 
 
ENTRY 1
 
(See note 5 for RF zones)
 
 ENTRY 2
 
(See note 5 for RF zones)
 
Response when system disarmed and zone is: 
Intact EOL 
RF zone normal 
Open 
RF zone N/A 
Shorted 
RF zn off-normal 
Auto  
Restore 
 
Vent Zone 
0 = normal 
1 = alarm  
2 = trouble 
3 = fault 
0 = normal 
4 = alarm 
8 = trouble  
12 = fault
 
 
 0 = normal 
 1 = alarm 
 2 = trouble 
 3 = fault 
0 = no 
4 = yes  
0 = no 
8 = yes 
Entry 1 = EOL + Open  
 Entry 2 = Short + auto restore + vent zone  
 
ENTRY 3
 
(See note 5 for RF zones)
   
ENTRY 4
 
(See note 5 for RF zones)
 
Response when armed STAY and zone is: 
Intact EOL 
RF zone normal
 
Open 
RF zone N/A
 
Shorted 
RF zn off-normal
 
Byp. when 
disarmed 
Byp. when 
armed 
0 = normal 
1 = alarm  
2 = trouble 
3 = fault
 
 
0 = normal 
4 = alarm 
8 = trouble  
12 = fault
 
 
 0 = normal 
 1 = alarm 
 2 = trouble 
 3 = fault 
0 = no 
4 = yes  
 
0 = no 
8 = yes 
 
Entry 3 = EOL + Open  
 Entry 4 = Short + byp. disarmed + byp. armed 
 
ENTRY 5
 
(See note 5 for RF zones)
   
ENTRY 6
 
(See note 5 for RF zones)
 
Response when armed AWAY and zone is: 
Intact EOL  
RF zone normal
 
Open  
RF zone N/A
 
Shorted 
RF zn off-normal
 
Dial Delay 
(see field *50) 
Fault Delay 
(see field *87) 
0 = normal 
1 = alarm  
2 = trouble 
3 = fault  
0 = normal 
4 = alarm 
8 = trouble  
12 = fault  
 0 = normal 
 1 = alarm 
 2 = trouble 
 3 = fault 
0 = no 
4 = use delay  
 
0 = no 
8 = use delay 
 
see note 1 
Entry 5 = EOL + Open 
 Entry 6 = Short + dial delay + fault delay 
 
ENTRY 7
 
 
ENTRY 8
  
Display Faults  
Power Reset/ 
Verification 
Use Entry 
Delay 1/2 
Use Exit 
Delay 
Respond as 
Interior Type 
0 = show alarms 
when armed 
& disarmed 
1 = don’t show 
alarms when 
armed 
(show 
alarms, trbles, 
faults when 
disarmed)
 
3 = never show 
any alarms, 
trbles, faults 
0 = no 
4 = power reset 
after fault 
(by code + OFF)
12 = verification 
 (see 
zone 
type 16) 
 0 = no 
 1 = delay 1 
 2 = delay 2 
0 = no 
4 = use exit 
delay  
0 = no 
8 = yes  
 
see note 2 
Entry 7 = fault display + power 
reset/verification 
Entry 8 = entry delay 1/entry delay 2 + exit delay +   
 interior zone type 
 
ENTRY 9
 
 
ENTRY 10
 
Alarm Sounds 
Use Bell 
Timeout 
Respond as 
Fire Zone 
Trouble  
Sounds 
Chime when 
Chime Mode On
0 = none 
1 = steady 
keypad 
2 = steady bell 
and keypad 
3 = pulsing bell 
and keypad 
0 = no 
4 = yes  
 
see fields *32, 
*33 
0 = no 
8 = yes  
 
see zone type 
09; see note 4 
 0 = none 
 1 = periodic 
beep 
 2 = trouble 
beeps 
0 = no 
4 = yes  
Entry 9 = alarm sounds + bell timeout + fire zone 
 Entry 10 = trouble sounds + chime
 
Entries for Fields *182 and *184 
Entry  Zone Type 90 
Zone Type 91 
 
  (field *182) 
  (field *184) 
 1 
 2 
 3 
 4 
 5 
 6 
 7 
 8 
 9 
10 
 
To calculate the value for each entry: 
Simply add the values of the selected options 
in each of the entry’s columns (one option per 
column). For example, to program Entry 2 for 
“alarm response to short,” “auto restore on,” 
but not a “vent zone,” enter 5 (“1” for alarm 
short + “4” for auto restore yes + “0” for vent 
zone no). 
 
 
OPEN
SHORTED
INTACT
EOL
ZONE-003-V0
 
Zone Conditions Represented  
in Entries 1-6 
 
NOTES: 
1.  Do not use the “fault delay” option with a 
configurable zone type if it is set for an 
entry or exit delay, otherwise 
unpredictable results may occur. 
2.  To create an interior type zone, select 
“respond as interior zone type” (entry 8, 
interior type = yes), and set zone 
response to “fault” in entries 3-4 to ensure 
fault displays; do not set as “normal,” 
“alarm,” or “trouble.” 
3.  Do not set fire zones to respond as a 
“fault” (entries 1-6), otherwise faults will 
not display unless the [
∗] key is pressed. 
4.  4219/4229 modules must use EOLRs or 
unpredictable results may occur. 
5.  RF Zones: The “open” option in entries 1, 
3, and 5 is not applicable for RF zones. 
Use the “intact EOL” option for normal RF 
zone conditions and “shorted” for off-
normal RF zone conditions. 
6.  a. Zone-Doubling/Double-Balanced: A 
short on either zone of a zone-doubled 
pair or on a double-balanced zone 
causes a tamper condition. 
 
b. For double-balanced zones, this entry 
must be “0.” 
 
c. For zone-doubled zones, both zones 
of the doubled pair must be assigned 
the same response to a short.