First Alert FA148CPSSIA Benutzerhandbuch

Seite von 40
– 25 – 
 
 
 
 
XX OUTPUT TYPE 
DELETE 0 
 
Output Type  
0 = delete  
1 = relay on 4204/4229 
module  
2 = Powerline Carrier device 
(X-10) 
[
∗] to continue
 
 
Select whether this is a relay or a Powerline Carrier (X-10) 
device. 
If Powerline Carrier is selected, go to “A” prompt. 
If relay is selected, skip to “B” prompt.
 
 
 
 
“A” 
XX UNIT No.  
 yy 
 
Unit Number  
01-16 = predefined address 
[
∗] to continue
 
 
(prompt appears
 
if X-10 is selected)
  
Enter the unit code (set at the device) and press [
∗].  
The system returns to the Output Number prompt.
 
 
 
 
“B” 
XX MODULE ADDR 
07-15 yy 
 
Module Address  
07-15 = predefined address 
[
∗] to continue
 
 
(prompt appears
 
if relay is selected)
  
Enter the predefined address for this module as listed below. 
Make sure the module’s DIP switches are set to the selected 
address. 
Module Addresses 
Address Module 
 
  07 
1st 4229 (with zones 09-16) 
  08 
2nd 4229 (with zones 17-24) 
 09
 
3rd 4229 (with zones 25-32) 
 10
 
4th 4229 (with zones 33-40) 
 11
 
5th 4229 (with zones 41-48) 
 12 
1st 4204 
 13 
2nd 4204 
 14
 3rd 
4204 
 15
 4th 
4204 
† These addresses apply to FA168CPS only.
 
 
 
 
XX REL POSITION 
1-4 zz 
 
Relay Position 
1-4 = relay position 
[
∗] to continue
 
 
This is the actual (or physical) relay number with respect to the 
Relay Module upon which it is located. For 4204 modules, relay 
numbers are 1-4. For 4229 modules, relay numbers are 1-2. 
The system returns to the Output Number prompt for 
programming the next device.
 
 
 
 
 
∗∗∗∗80 OUTPUT FUNCTION MENU MODE
  
(press 
∗∗∗∗80 while in Programming mode)  The Output Definition Worksheet is on page Error! Bookmark not defined.
Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output 
devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified 
by an output function number, and includes the following components: 
 
Output Definition Components 
Component
 
Description
 
Output Function No.
 
A reference number that defines an output’s characteristics.
 
Activated By
 
Determines whether the initiating event occurs on a zone, a zone list, or a zone type.
 
Event
 
Event that triggers the output action. Can be an event occurring on a specific zone number or a 
zone list, or a specific zone type.
 
Partition
 
If the output is activated by zone type, this defines the partition in which the programmed event is 
to cause the device action.
 
Output Action
 
Defines the action of the relay/X-10 device when the defined event occurs. Can close for 2 
seconds, stay closed until reset, continuously pulse (1-second close-open-close-open, etc.), 
toggle the device state, or activate for a defined duration (set in data field *177).
 
Output No.
 
Assigns this function to a specific output number (defined in *79 Menu Mode). This is the output 
number that will perform this function upon the triggering event. Note that each defined function is 
associated with only one output number. This means that if more than one output device needs to 
perform this particular function, you need to define another output function number with the same 
attributes, but assign the appropriate output number. (i.e. output devices can be assigned more 
than one function number, but each function number can only be assigned a single output 
number.
 
 
For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to output number 2 (as 
programmed in *79 Menu Mode), program the following in *80 Menu Mode: 
Prompt Entry 
Output Funct. # 
=  
01 (assuming this is the first output function) 
Activated By: 
3 (zone number) 
Enter Zn No. 
04 (requires 2-digit zone numbers) 
Output Action 
3 (continuous pulse) 
Output Number 
02 (device mapped in *79 Menu Mode)