23.6  Cross Zoning
Caution must be taken when cross zoning devices to ensure that the Cross Zone Time is long enough to
allow an intruder to trip both devices before it expires. A Cross Zone Time that is too short may allow an
intruder to trip the devices and allow only a zone fault report be sent to the central station.
When a Cross Zoned zone trips a FAULT report is sent to the SCS-1R Receiver. When two Cross Zoned zones
trip within the Cross Zone Time, both zones send ALARM signals to the receiver. For example, if zones 1
and 2 are Cross Zoned zones, and only zone 1 trips, a FAULT report is sent to the receiver for zone 1. If
zone 1 trips and zone 2 trips within the Cross Zone Time, an ALARM report is sent to the receiver for zone
1 and zone 2.  
23.7  Events Manager
The Events Manager allows you to delay sending 
certain reports to the central station receiver.  
Reports can be kept in the panel memory until 
overwritten by new activity or held until the 
memory buffer reaches 50 events or 50 door access 
granted events. When the buffer is full, the panel
automatically sends the stored reports to the 
central station receiver.  The table lists the panel 
reports you can delay using the Events Manager 
option.  
23.8  User Profiles
A profile defines the authority of each user
code in the system. Profiles are programmed in
the Keypad User Menu. Several characteristics
associated with each User Profile define its
authority within the system.  To effectively 
program an XR500 Series system, you must understand the interrelationship between profiles, devices,
output groups, and areas. Below is a brief explanation of the User Profile elements. For more information
about user profiles, refer to the User Profiles Record and the XR100/XR500 User’s Guide (LT-0683).
Note: Profiles cannot be changed via keypad in an All/Perimeter or Home/Sleep/Away system. Use the
default profiles 1 through 10.
Profile Number - Each profile may be assigned a unique number from 1 to 99.
Profile Name - Each profile may be assigned a 32-character name. The Profile Number is the default name.
Area Number - Each profile may be assigned specific areas of the system for arming and disarming.
When creating profiles 1 to 98, NO areas are assigned by default. The default for profile 99 is ALL areas
assigned. Profile 99 is preprogrammed in the system at the factory.
Access Area Number - Each profile may be assigned door access area assignments. Default for profile 1 to 98
is NO areas assigned. Default for profile 99 is ALL areas assigned. Profile 99 is preprogrammed at the factory.
Output Group Assignment - Each profile may be assigned an output group number from 1 to 10. Default
for profile 1 to 98 is NO output group assigned. Default for profile 99 is output group
10.  Your system may 
by programmed to turn on an output group at certain keypads when door access occurs.
User Menu Assignments - Each user profile may have any of the menus assigned to it as shown in the
following User Profile Record. The User Profile Record lists the user menu profile assignments and the
system functions users are allowed to access based on the profile numbers assigned to their codes.
Always make sure that at least one administrator in your system has a profile with
all authorities and 
areas.
23.9  User Profiles Record
This User Profiles Record can be used as a tool when programming Devices, Profiles, Areas, and Output
Groups. Because these programming options are interrelated, use this sheet to plan the system before you
begin the installation and programming process.
Report Type
Immediately Delayed
Alarm
Y
Trouble
Y
Restore
Y
Opening
Y
Closing
Y
Bypass
Y
Reset
Y
Supervisory
Y
Add Codes
Y
Delete Codes
Y
Change Codes
Y
Permanent Schedule Change
Y
Temporary Schedule Change
Y
Door Access
Y
Door Access Denied 
Y
Late to Close
Y
Force Armed Zone
Y