ISACC Instruction Manual
LIMITS
ISACC allows you to set high and low limits for inputs defined as 4-20mA analog, 0-5V
analog, pulse count, temperature, table, or user defined. The limits are used to determine when
an input is in alarm. The command SET LIMITS prompts you to enter these values. NOTE:
An input defined as N.O. or N.C. does not have a high or low limit. ISACC will display N/A
for that input. An input defined as pulse count can only have a high limit.
analog, pulse count, temperature, table, or user defined. The limits are used to determine when
an input is in alarm. The command SET LIMITS prompts you to enter these values. NOTE:
An input defined as N.O. or N.C. does not have a high or low limit. ISACC will display N/A
for that input. An input defined as pulse count can only have a high limit.
To display the current programmed limits, type show limits after an ISACC prompt. You
may display a specific limit by typing show limits followed by the input number.
may display a specific limit by typing show limits followed by the input number.
ISACC>show limits
HIGH AND LOW ANALOG LIMITS
IN01 = "LOW WELL FLOAT " = N/A
IN02 = "HI SUMP FLOAT " = N/A
IN03 = "Input #3 " = N/A
IN04 = "FLOW RATE (GPM) " = LOW = -9999 HIGH = 9999
IN05 = "WELL LEVEL (FT) " = LOW = -9999 HIGH = 9999
IN06 = "RESET " = N/A
IN07 = "Input #7 " = N/A
IN08 = "VOLTAGE " = LOW = -9999 HIGH = 9999
IN09 = "Input #9 " = N/A
IN10 = "Input #10 " = N/A
IN11 = "Input #11 " = N/A
IN12 = "Input #12 " = N/A
IN13 = "Input #13 " = N/A
IN14 = "Input #14 " = N/A
IN15 = "Input #15 " = N/A
IN16 = "Input #16 " = N/A
To program the low and high limits for analog or pulse count inputs, type set limits after an
ISACC prompt. Type a value and press ENTER to go to the next parameter. You may pro-
gram a specific limit by typing set limits followed by the input number.
ISACC prompt. Type a value and press ENTER to go to the next parameter. You may pro-
gram a specific limit by typing set limits followed by the input number.
ISACC>set limits
HIGH AND LOW ANALOG LIMITS
IN01 = "LOW WELL FLOAT " = N/A
IN02 = "HI SUMP FLOAT " = N/A
IN03 = "Input #3 " = N/A
IN04 = "FLOW RATE (GPM) " = LOW = -9999 >0001 HIGH = 9999 >0025
IN05 = "WELL LEVEL (FT) " = LOW = -9999 >0010 HIGH = 9999 >0150
IN06 = "RESET " = N/A
IN07 = "Input #7 " = N/A
IN08 = "VOLTAGE " = LOW = -9999 >0000 HIGH = 9999 >0110
IN09 = "Input #9 " = N/A
IN10 = "Input #10 " = N/A
IN11 = "Input #11 " = N/A
IN12 = "Input #12 " = N/A
IN13 = "Input #13 " = N/A
IN14 = "Input #14 " = N/A
IN15 = "Input #15 " = N/A
IN16 = "Input #16 " = N/A