Praesideo 3.5 | Installation and User Instructions | 9 | System Configuration
en | 325
40.4.4 Submitting
Each page in the Configure section of the web interface 
contains a Submit button. Always click this button after 
making changes, otherwise the changes are lost. 
Clicking the Submit button, however, does not mean 
that the changes are saved (see section 40.4.5).
40.4.5 Saving
Proceed as follows to save the current configuration:
1 Go  to  Configure > Save. Then a (limited) confidence 
check on the configuration is executed automatically. 
Now there are three different possibilities:
When there are no issues found, and the configu-
ration is done on-line, three buttons are displayed to 
enable the user to Save the configurationRestart the sys-
tem
 or Save the configuration and restart the system. See 
figure 40.5. When the configuration file is saved to the 
network controller, the configuration is not activated 
until the network controller is restarted. If the new 
configuration must be saved and activated, click the 
Save the configuration and restart the system button.
When there are no issues found, and the configu-
ration is done off-line, only one button is displayed to 
enable the user to Save the configuration. Restarting the 
system is not possible when off-line. In case of an 
off-line configuration, by default the configuration file 
is saved in the Program Files\Bosch\Praesideo\target\rfa\cfg 
folder of the configuration PC, but other locations are 
also possible. This file can be transferred to the net-
work controller using the File Transfer application.
When there are issues found, a message is dis-
played indicating there are configuration issues to be 
resolved first. Still it is possible to ignore the errors 
and save the configuration anyway to continue the 
configuration at a later time. Only one button is dis-
played: Ignore errors and save configuration. See figure 
40.6.
2 Click the Save Configuration and restart the system 
button to activate the new configuration. The 
network controller will be restarted.
The Save Configuration and restart the system button is 
used for activating a new configuration that has been 
made on-line. But if a new configuration file has 
been made off-line and has been copied to the 
network controller then the Save Configuration and 
restart the system
 button should not be used because 
the network controller would only reload the existing 
(unchanged) configuration file. Instead click the 
Restart the system button or switch the network 
controller off and on again, then the network 
controller will load the replaced configuration file.
figure 40.5: Save window
figure 40.6: Ignore errors and save configuration win-
dow
Note
In Praesideo release 3.4 the processor reset 
identification has been extended for compliancy 
reasons. However this software modification will 
flag a Processor reset fault for all connected 
units when performing a Save the configuration 
and restart the system. This will happen for 
network controllers with a hardware release 
version HW 20.00 or older. These faults do not 
indicate a real fault, but are just the result of the 
restart-action and can safely be acknowledged 
and reset. From version HW 20.01 onwards, the 
network controller contains a circuit 
modification to prevent these unnecessary 
Processor reset faults.