PRESSURE TESTING GAS SUPPLY 
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG 
(3.5 kPa)
1.  Disconnect appliance with its appliance main 
gas  valve  (control  valve)  and  equipment 
shutoff valve from gas supply piping system. 
Pressures in excess of 1/2 psig will damage 
heater regulator.
2.  Cap off open end of gas pipe where equipment 
shutoff valve was connected.
3.  Pressurize  supply  piping  system  by  either 
opening propane/LP supply tank valve for 
propane/LP gas or opening main gas valve 
located on or near gas meter for natural gas 
or using compressed air.
4.  Check all joints of gas supply piping system. 
Apply a noncorrosive leak detection fluid to 
all joints. Bubbles forming show a leak.
5.  Correct all leaks at once.
6.  Reconnect  heater  and  equipment  shutoff 
valve to gas supply. Check reconnected fit-
tings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG 
(3.5 kPa)
1.  Close equipment shutoff valve (see Figure 16).
2.  Pressurize  supply  piping  system  by  either 
opening propane/LP supply tank valve for 
propane/LP gas or opening main gas valve 
located on or near gas meter for natural gas 
or using compressed air.
3.  Check all joints from gas meter for natural gas 
(see Figure 17) or propane/LP supply tank for 
propane/LP gas, to equipment shutoff valve 
(see Figure 18). Apply a noncorrosive leak 
detection fluid to all joints. Bubbles forming 
show a leak. 
4.  Correct all leaks at once.
PRESSURE TESTING HEATER GAS 
CONNECTIONS
1.  Open equipment shutoff valve (see Figure 16).
2.  For natural gas open main gas valve located 
on or near gas meter. For propane/LP gas open 
propane/LP supply tank valve.
3.  Make sure control knob of heater is in the OFF 
position.
4.  Check all joints from equipment shutoff valve 
to thermostat gas valve (see Figure 17 or 18). 
Apply a noncorrosive leak detection fluid to 
all joints. Bubbles forming show a leak.
5.  Correct all leaks at once.
6.  Light heater (see Operating Heater, page 14). 
Check all other internal joints for leaks.
7.  Turn off heater (see To Turn Off Gas to Ap-
pliance, page 15 or 16 depending on your 
model).
8.  Replace front panel.
Figure 18 - Checking Gas Joints for 
Propane/LP Gas
Figure 16 - Equipment Shutoff Valve
Equipment 
Shutoff 
Valve
Propane/LP 
Supply Tank
Thermostat Gas Valve
Open
Closed
Equipment 
Shutoff Valve
Figure 17 - Checking Gas Joints for 
Natural Gas
Equipment 
Shutoff 
Valve
Gas 
Meter
Thermostat Gas Valve