Heatcraft Refrigeration Products H-IM-CU Benutzerhandbuch

Seite von 24
17
Electric Defrost Troubleshooting
The electric defrost units are relatively simple and trouble-free in operation:
Timer
If the system does not go through its proper sequence , check timer 
operation through a defrost cycle. Check for loose wires or  terminals. Before 
replacing timer, check other components.
Operation of Paragon
Timer
To set time of day grasp knob which is in the center of the inner (fail-safe) dial 
and rotate it in a counter-clockwise direction.  This will cause the outer (24 
hour) dial to revolve.  Line up the correct time of day on the outer dial with 
the time pointer.  Do not try to set the time control by grasping the other (24 
hour) dial.  Place pins in the outer dial at the time of day that defrost  
is required.
Operation of Grasslin Timer
To set the time, turn the minute hand clockwise until the time of day (and 
AM or PM) on the outer dial is aligned with the triangle marker on the inner 
dial. Do not rotate minute hand counter-clockwise. Move the white tab 
(tripper) on the outer dial outward at each desired initiation time. Each white 
tab (tripper) is a 15 minute interval and provides 15 minutes of defrost. For 
longer defrost duration, move additional tabs (following in time) from the 
initiation tab. For example, if a 45 minute defrost is to start at 7:00 AM, move 
the tabs outward that lie between 7:00 - 7:15, 7:15 - 7:30 and 7:30 - 7:45 on 
the AM side of the dial. The defrost will initiate at 7:00 AM and time terminate 
at 7:45 AM (if temperature termination does not occur first).  For models with 
plastic cover on timer assembly; re-install cover after adjustment.
NOTE:
After correcting faulty condition it is essential that the coil and unit be 
free of ice before placing unit back on automatic operation.
NOTES:
1.  Lockout relays or normally closed switch of auxiliary contact on the 
compressor contactor may be wired to defrost contactor.  Its purpose 
is to prevent energizing of the defrost heaters until the compressor has 
pumped down and stopped, thus keeping power demand to a minimum. 
2.  If the control voltage is to remain energized for any period of time with 
the compressor disabled, remove the defrost clock pins to prevent the 
defrost heaters from energizing.   
3.  A Preventative Maintenance schedule should be set up as soon as 
possible after start-up to maintain equipment integrity.
General Sequence of Operation
Refrigeration Cycle
Power is supplied to the timer at terminals “1” and “N”.
The fan delay and the defrost termination thermostat is closed in the fan  
 
delay position and open in the defrost termination position.  
 
The unit cooler fans run continuously.
The defrost heaters are off.
The room thermostat closes when the temperature rises above the  
 
 
desired setting.
The liquid line solenoid is energized and opens, which allows  
 
 
liquid refrigerant to flow through the unit cooler.  
The low pressure control closes when the suction pressure rises 
 
above the cutin setting of the control.  
On systems with oil pumps, the oil safety control is closed. If the  
 
 
net oil pressure is less than 9 PSIG for more than 120  
 
 
 
seconds, the oil safety opens, thus breaking the circuit  
 
 
 
to the compressor contactor holding coil. The compressor will  
 
 
not operate. This control is reset manually and must be  
 
 
 
reset before the compressor can be restarted.  
The compressor contactor closes. The compressor and condenser 
 
fan start simultaneously.  
The room temperature gradually decreases to the desired temperature.
Once the desired temperature is reached, the thermostat opens and the  
 
liquid line solenoid closes, stopping refrigerant flow through  
 
the evaporator.  
Suction pressure decreases and the compressor contactor opens 
 
when the pressure drops below the cutout setting on the low  
 
 
pressure control. The compressor and condenser fan stop running.
This cycle is repeated as many times as necessary to satisfy the  
 
 
room thermostat.
Frost starts to form on the evaporator coil and continues to form  
 
 
until the defrost cycle is initiated.
Defrost Cycle
The defrost cycle starts automatically by the timer at predetermined    
 
times. Typical settings are two to four defrost cycles per day for freezers.  
 
For heavier frost loads additional settings may be required.
Switch “2” to “4” opens in the timer which breaks the circuit to the room  
 
thermostat, liquid line solenoid, and evaporator fan motors, allowing    
 
the compressor to pump down and shut off.  Simultaneously  
 
 
switch “1” to “3” closes in the timer allowing current to flow to one side    
 
of the  defrost heater contactor. When the compressor  
 
 
 
shuts off, an auxiliary contact will send power to the contactor holding   
 
coil; thus, energizing the defrost heaters.
The heaters raise the temperature of the coil to 32˚F causing the frost to  
 
melt off the coil.
When the coil warms to 45˚F to 55˚F, the defrost termination thermostat  
 
closes, which allows current to the switching solenoid in the timer  
 
 
allowing the refrigeration cycle to begin again.
The evaporator heaters are off.  If the termination thermostat fails to    
 
close, the fail-safe set on the timer will terminate defrost.
The low pressure control closes and the compressor will start.  
When the coil temperature reaches 23˚F to 30˚F, the fan 
 
delay closes. This allows the current to flow to the fan  
 
motors. The fan motors start running.
The system will now operate in the refrigeration cycle until another  
 
 
defrost period is initiated by the timer.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
1.
2.
3.
4.
5.
6.
7.
8.