CSB HRL634W Merkblatt

Seite von 2
Cells per unit
Voltage per unit
Capacity
Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging
Current Limit
Equalization and Cycle Service
Self Discharge
Terminal
Container Material
3
6
34W @ 15min-rate to 1.67V per cell @25
o
C(77
o
F)
Approx.1.32 kg(2.91 lbs)
130A(5sec)
Approx. 10
m
25
o
C±3
o
C (77
o
F±5
o
F)
6.75 to 6.9 VDC/unit Average at 25
o
C(77
o
F)
3.4A
7.2 to 7.5 VDC/unit Average at 25
o
C(77
o
F)
CSB Batteries can be stored for more than 6 months at
25
o
C (77
o
F). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
F2-Faston Tab 250
ABS(UL 94-HB/File E50263)*Flammability resistance of
(UL 94-V0/File E88637) can be available upon request.
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15 ~40 (  5 ~104 )
Storage: -15 ~40 ( 5 ~104 )
Constant Power Discharge Characteristics Unit:W (25
,77 )
Constant Current Discharge Characteristics Unit:A (25
,77 )
HRL 634W
6V 34W
Specification
Powered by
HRL 634W is specially designed for high efficient discharge 
application. Its characteristics are high energy density, small 
footprint and high discharge efficiency. It can be used for more 
than 260 cycles at 100% discharge in cycle service, up to 8 
years in standby service.
Width (W)
Dimensions : 
Unit: mm (inch)
Overall Height (H)
Container height (h)
Length (L)
98.3±1 (3.9±0.08)
94±1 (3.7±0.08)
151±2 (5.94±0.08)
34±1 (1.34±0.04)
F.V/Time
2MIN
4MIN
6MIN
8MIN
10MIN
15MIN
20MIN
30MIN
60MIN
90MIN
1.60V
60.4
47.4
37.6
30.9
26.6
18.7
14.4
10.3
5.84
4.66
1.67V
56.5
44.4
35.4
29.3
25.2
18.6
14.3
10.2
5.80
4.63
1.70V
54.9
43.1
34.2
28.6
24.6
18.5
14.2
10.1
5.78
4.62
1.75V
51.9
40.7
32.3
27.0
23.8
18.3
14.1
10.0
5.74
4.57
1.80V
48.9
37.9
30.6
25.8
23.0
18.1
13.9
9.94
5.69
4.52
1.85V
45.4
35.1
28.6
24.6
22.0
17.9
13.8
9.84
5.65
4.47
F.V/Time
2MIN
4MIN
6MIN
8MIN
10MIN
15MIN
20MIN
30MIN
60MIN
90MIN
1.60V
327
260
209
175
150
110
84.0
60.7
34.6
27.7
1.67V
312
246
197
167
143
109
82.6
60.3
34.5
27.6
1.70V
305
240
192
163
140
108
82.0
59.7
34.4
27.5
1.75V
292
228
183
155
135
104
81.0
59.3
34.2
27.3
1.80V
278
215
173
147
129
100
80.0
58.9
33.9
27.1
1.85V
265
203
164
139
123
96.0
79.0
58.1
33.7
26.9
RA0911
CSB-manufactured
VRLA 
batteries are UL-
recognized components
under UL924 and UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
 
(http://www.csb-battery.com) 
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified