Sterling 25001301 Benutzerhandbuch

Seite von 12
 
Table 1. Fluid Cooler Internal Volume and Weight 
Fluid 
Cooler 
Fan Configuration 
Number 
of 
Fans 
Number 
of 
Rows 
Internal 
Volume 
Gallons 
Approximate 
Net Weight 
(Lbs.) 
1 x 2 
6.7 
1540 
1 x 2 
9.2 
1590 
1 x 2 
11.8 
1600 
1 x 3 
13.0 
2360 
1 x 3 
16.7 
2420 
1 x 4 
16.7 
3150 
1 x 4 
21.7 
2190 
1 x 5 
20.4 
3510 
1 x 5 
26.6 
3990 
1 x 6 
31.6 
4790 
2 x 2 
13.5 
1540 
2 x 2 
18.5 
1620 
2 x 2 
23.5 
1760 
2 x 3 
25.9 
2420 
2 x 3 
33.4 
2480 
2 x 4 
33.3 
3230 
2 x 4 
43.3 
3510 
2 x 5 
40.7 
4040 
2 x 5 
53.1 
4390 
2 x 6 
63.1 
5270 
 
Electrical Wiring 
The electrical installation should be in accordance with 
National Electrical Code, local codes and regulations. Proper 
overcurrent protection should be provided for the fan motors. 
Wiring diagrams shown are only basic and do not show fuses, 
disconnect switches, etc., which must be provided in the field. 
All standard motors have internal inherent overload 
protectors. Therefore, contactors can be used instead of 
starters requiring thermal protectors, eliminating the problem 
of furnishing the proper heating elements. 
All dry coolers or units are furnished with either single-
phase or three-phase fan motors which are identified by the 
unit dataplate. 
Electrical leads from each motor terminate at the unit 
junction box. Field connections must be made from these leads 
through a contactor, fuse and disconnect in accordance with 
local, state and national codes. 
Three-phase motors must be connected to three-phase 
power of voltage to agree with motor and unit dataplate. 
The motors are wired into a common junction box. The 
motors must be checked for proper rotation. Be sure to check 
that motor voltage and control connection agree with electric 
services furnished. 
 
4