3.2 Switch 
Settings 
The two DIP-switches located on the circuit board are used to program the operator to operate in 
various modes and to turn on or off various operating features.  Whenever a switch setting is 
changed, power to the operator must be turned OFF and then turned back on for the new setting to 
take affect.  Check and review ALL switch settings prior to applying power to the operator.   
CAUTION:  Switches on the circuit board are numbered right to left, not left to right. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
SW 1 (RIGHT SWITCH) 
SWITCH FUNCTION  SETTING 
DESCRIPTION 
1 Direction 
OFF 
ON 
Changes open / close direction of operator. 
2 Auto 
Close 
Timer 
OFF 
ON 
Auto-close timer is OFF.  Manual input required to close gate. 
Auto-close timer is ON.  Adjustable from 1-23 seconds. 
3 Open 
Loop 
Output 
OFF 
ON
 
Switches logic-level output of EXIT loop port to terminal 4. 
Normal Setting
.  Control board responds internally to loop 
detector plugged into exit loop port. 
4 & 5 
Relay & LED 
4-OFF    5-OFF
4-OFF    5-ON 
4-ON     5-OFF 
4-ON     5-ON 
Relay activated and LED on when gate is FULL OPEN. 
Relay activated and LED on when gate is NOT CLOSED. 
Relay activated and LED on when gate is OPENING and OPEN. 
Relay activated and LED on when gate is OPENING or CLOSING. 
6 Warn 
Before 
Operate 
OFF
 
ON 
Normal setting
.  
Alarm will sound 2-3 seconds prior to the gate starting. 
7 Reverse 
 
Stop 
OFF 
 
ON 
Normal Setting
.  Input to terminal 7 will REVERSE gate during 
close cycle. 
Input to terminal 7 will STOP gate during close cycle. 
8 Quick 
Close 
OFF 
ON 
Normal gate operation. 
Opening gate will stop and begin to close as soon as all reversing 
inputs (loops, beams) are clear regardless of the open position of 
the gate. 
 
 
 
 
 
 
 
 
 
 
 
 
 
SW 2 (LEFT SWITCH) 
SWITCH FUNCTION  SETTING 
DESCRIPTION 
1 Self 
Test 
(see note 1) 
OFF
 
ON 
Normal setting.
 
Run self-test – bench test only. 
2 Open 
Uphill 
OFF
 
ON 
Normal setting.
 
Turn ON if gate opens in an uphill direction. 
3 Open 
Downhill 
OFF
 
ON 
Normal setting
Turn ON if gate opens in a downhill direction. 
4 Spare 
OFF
 
ON 
Normal Setting
 
NOTES: 
1.  Do not run the self-test while the gate operator is connected to the gate.  This self-test 
feature is designed for bench-testing only. 
Page 
34
  
9210-065-H-8-08