Gianni Industries P-MU-GS705N-30 Merkblatt

Seite von 2
Copyright Gianni Industries, Inc. All Rights Reserved.
Publish
P-MU-GS705N-30 Ver. C
:2007.07.17
2-1
GS-705N Shear Lock Installation Instruction
Specifications
Connecting Diagram
Caution:
Make sure that the "+" and "-"
wire are connected correctly.
Failure to observe polarity will
result in a short circuit and is
n o t c o v e r e d b y p r o d u c t s
warrant.
Dimensions
Unit: mm
30
30
32
6
251
267
Push-off button
Armature vertical
adjustment screws
Locking Bolt
Keep Hole
Keep Hole
Magnet Assembly
Armature Assembly
GS-705N-30
3.5
5.9
Locking Bolt
+
-
Power
supply
Magnet bond sensor output
SPDT relay : 1A@30 VDC
+
-
N.O.
COM.
N.C.
Power
Input
Magnet
bond
sensor
output
Vo l t a g e S e l e c t i o n j u m p e r s
Check jumper settings before
connecting the lock to 24 VDC
input power. Damage to the
lock may result from incorrect
jumper settings.
12Vdc
24Vdc
Holding Force
Power Input
Door Gap
Operating Temper.
Current Draw
Monitoring Output
Finish
Up to 2700 lbs (1226 Kg) in shear.
12/24 VDC selectable via jumpers +10%
over voltage is acceptable , under voltage
will reduce holding force.
0.35 A@12 VDC; 0.17 A@24 VDC The unit
does not require initial voltage increase to
operate.
M a g n e t a n d A r m a t u r e : Z i n c p l a t e d
Housing: Black powder coated
SPDT rating
1 AMP@30 VDC
2mm
-30C to +50C
Magnet bond sensor output,
Unbalanced air conditioning (stack pressure) can hinder door alignment and must be corrected to help insure positive locking. It
is important to note that the Shear Locks need a regulated 12V DC (or 24VDC) at the lock, and use the highest quality door closer
only.
Positive centering door closers are required for all double acting door applicators to help attain consistent dead center
alignment. Also the door latching problems must be corrected prior to installation.
Control Device
N.C. contact or Access Relay
Install the magnet assembly into the door
frame before installation the armature assembly
into the door leaf. The magnet assembly requires
space to run wires, as wall as space for the
recesses portion of the unit. However, make sure
that the position selected for the magnet
assembly leaves enough room on the door to
install the armature assembly.