Excel 500-XCL5010 Cable Specifications 
MMI Cables 
Ready-made cables with the shield already connected to the 
computer module plug end are available for the connection of 
external MMIs. 
Table 24. Cable specifications 
MMI type 
Cable 
Length 
XI582 (remote MMI) 
XW582 
17 ft (5m) 
XI584 (PC-based MMI) 
XW585 
17ft (5m) 
For connection to the XI584, a standard null modem cable 
may be used. 
TO EXCEL 500-XCL5010 
XW582 
TxD  YELLOW 
+5VE BROWN 
RxD 
GND 
GREEN 
WHITE 
XI582 
SHIELD 
TxD 
+5VE 
RxD 
GND 
YELLOW 
BROWN 
GREEN 
WHITE 
TO EXCEL 500-XCL5010 
TO XI584 
Fig. 89. Excel 500-XCL5010 / MMI cable details 
EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Modem or ISDN Terminal Adapter Connections 
For remote communications, a modem or ISDN terminal  
adapter can be connected directly to the serial port of the  
Excel 500-XCL5010 Controller.  
The serial port of the Excel 500-XCL5010 controller accepts a  
standard modem cable with a female 9-pin connector. Use  
the cable that is supplied with the modem/ISDN terminal  
adapter.  
The communication speed is 9600 baud by default but can be  
set as high as 38.4 Kbaud.  
For more details, see section "Remote Communications" on  
page 43.  
Changing Between MMI and Modem Connection 
The Excel 500-XCL5010 will detect when an MMI or 
modem/ISDN terminal adapter is connected and will adjust 
the communication speed automatically according to the 
preset values. This automatic detection can take up to 5 
seconds. 