Chapter 6: Maintenance 
48 of 58 
 
6-12  Regeneration Monitor Advanced Programming 
The regeneration monitor has three menu levels, numbered 0 through 2. Each menu level allows  
specific parameters to be viewed and/or set.  
Moving Between Levels 
Level 0, the RUN mode, is the default and automatically appears when the dryer is powered up. To 
move to Level 1, press and hold 
 for 2 seconds. When Level 1 is reached, press and hold both 
 
and 
 for 1 second to move up a level, or move back to RUN mode by pressing 
  for 1 second. 
See the flow chart below. 
 
Comparative output settings (when security is enabled)
Output hysteresis
Input shift value
Linear output range
Security protection
Sensor type
Display unit (°F/°C)
Display refresh time
Communication unit
Process temperature
Comparative output settings (when security is disabled)
Level 0
Level 1
Level 2
Press 
2 sec.
Press 1 
sec.
Press 
1 sec.
+
Press 1 
sec.
Press 
1 sec.
+
 
 
 
 
 
LEVEL 0 
In this, the default level, the present regeneration 
bleed air temperature is displayed, plus the 
monitor’s four setpoints can be viewed and 
changed.  
If security is enabled, the setpoints cannot be 
changed. They may be reviewed by pressing 
If security is disabled, the setpoints can be 
changed on this level by using 
 and 
When the desired setpoint is displayed, press 
 
to move to the digit you want to change, and use 
 to change the digit. Then press 
 to save 
the new setting to memory and to move on to the 
next setpoint. 
LL Set Value
Low Regen Temp Alarm
L Set Value
Regen Blower Shutdown Temp
H Set Value
Closed Loop Regen Cool Down Temp
HH Set Value
Heater Cut Off Temp
Present Value (PV)
Regen Bleed Air Temp