Clearing the Stored PPM Log, Alarms & Faults Data 
Up to 200 refrigerant gas ppm measurements, and 30 alarm and fault events are stored by the monitor.  
To clear stored data, first display the data to be cleared by using the PPM LogAlarms or Faults 
function (Pages 15). Next, press and hold down the Right Arrow Keypad button, and then press the 
ENTER button. A single, long tone should be heard when the data has been successfully cleared. 
 
Entering Custom Refrigerant Calibration Values 
In addition to the 24 refrigerant gases available for selection, a custom gas can be added by using the 
CUST K1, K2 & K3 function. Before using this function, the user must contact the factory and provide 
information about the gas to be monitored. The factory will then supply values for K1, K2, and K3, which 
are the coefficients of a polynomial equation that represent the calibration curve of the custom gas. 
From the Data Display screen, use the Keypad buttons to place the arrow (>) on the display next to the 
CUST K1 function. Then press ENTER to display the CUSTOM CAL K^1 screen. Use the Keypad 
buttons to enter the 1
st
 coefficient value (K1) as received from the factory. Press ENTER to save this value 
in memory. 
Repeat the above procedure to enter the values for K2 and K3. 
Select the custom gas for monitoring by using the GASTYPE function (Page 17) and selecting CUSTOM
 
Reset to Factory Default Settings 
IMPORTANT!
 Performing this function will wipe out all program parameters, alarms, faults, and ppm 
log files. 
Press and hold down switch SW3 inside the HGMSZ (Page 8). Cycle AC power OFF then ON. Listen for 
beep and then release switch. If needed, reprogram the HGMSZ to the desired settings. 
Factory Default Settings 
 
Parameter Factory 
Default 
4–20 mA Factor ........................ 0.016 mA/ppm 
Bench Voltage........................... 4.200 
Calibration Factor.................... 1.000 
Evacuate Alarm........................ 500 ppm 
Gas Type ................................... R-134a 
Leak Alarm............................... 100 ppm 
Log Interval .............................. 10 minutes 
Silence Timeout........................ 300 seconds (5 minutes) 
Spill Alarm................................ 300 ppm 
Squelch...................................... 0 ppm 
Zone Temperature.................... 25°C