Sierra Monitor Corporation 4101 Merkblatt

Seite von 2
Gas Sensor Modules
Electrical Data
Loop Type
3 wire
Loop Resistance
800 Ohm with 28VDC
400 Ohms at 21 VDC (4101-02)
Input Voltage DC
14-30 VDC (20-30VDC 4101-02)
Input Current
40 mA (80 mA 4101-02)
Input Power Max
1.4W (2.3W 4101-02)
Signal Output
4-20 mA DC linear (trouble 0 mA)
Operating Pressure
  +10% (variation from ambient)
Specifications
Cross Sensitivity Data
Model
Gas
                                     Reading from 100 PPM of interfering gas
Number
type
CO
H
2
S
Cl
2
H
2
SO
2
NO
2
NO
HCl
HCN
C
2
H
4
4101-04
CO
100
5
 0
<20
0
0
6
0
0
<50
4101-05
H
2
S
<2
100
-20
<0.1
<15
-15
0
0
0
0
4101-06
Cl
2
0
<-10
100
0
0
105
0
0
0
0
4101-10
SO
2
<1
0
-40
0
100
-100
0
0
15
0
4101-12
NO
2
0
-20
90
0
0
100
0
0
-3
0
4101-13
CO
100
350
0
<60
60
-60
25
0
0
<75
4101-16
CO
100
0
0
0
0
0
0
0
0
35
4101-19
NO
0
35
0
0
5
25
100
15
0
0
4101-21
HCl
0
75
-10
0
35
-2
0
100
-8
0
4101-22
HCN
<0.5
-50
0
160
-190
-5
100
<1
4101-27
C
2
H
4
O
Ethanol
55
(ETO)
Toluene
20
Methyl-ethyl-ketone
10
Carbon Monoxide
40
Sierra Monitor Corp.  1991 Tarob Ct., Milpitas, CA 95035, USA, 408-262-6611,  800-727-4377,  FAX: 408-262-9042
Web Site:  http://www.sierramonitor.com           E-Mail:  sierra@sierramonitor.com
Gas Type
Model
Sensor
Range
Units
Resolution Response Sensor
        Operating Range
Time (1)
Life (2)
        o
F
        o
C
    RH
Combustibles
4101-02
Catalytic
0-100
%LEL +/-3% F.S.
(3)
3 Yrs
-40 to 167 -40 to 75
10 - 95%
Oxygen
4101-03EL EC
0-25
% Vol
+/-0.1%
<10 sec.
2 Yr
5 to 122
-15 to 50
5 - 99%
Carbon Monoxide
4101-04
EC
0-500
PPM
1.0 PPM
<25 sec
2 Yrs
-4 to 122
-20 to 50
15 – 90%
Hydrogen Sulfide
4101-05
EC
0-100
PPM
0.1 PPM
<30 sec
2 Yrs
-40 to 122 -40 to 50
15 – 90%
Chlorine
4101-06
EC
0-10
PPM
0.1 PPM
<60 sec
2 Yrs
-4 to 122
-20 to 50
15 – 90%
Sulfur Dioxide
4101-10
EC
0-100
PPM
0.5 PPM
<20 sec
2 Yrs
-4 to 122
-20 to 50
15 – 90%
Nitrogen Dioxide
4101-12
EC
0-20
PPM
0.2 PPM
<35 sec
2 Yrs
-4 to 122
-20 to 50
15 – 90%
Carbon Monoxide 4 4101-13
EC
0-1000
PPM
0.5 PPM
<35 sec
2 Yrs
-4 to 122
-20 to 50
15 – 90%
Carbon Monoxide     4101-16
EC
0-2000
PPM
0.1 PPM
<35 sec
2 Yrs
-4 to 122
-20 to 50
15 – 90%
Nitric Oxide
4101-19
EC
0-20
PPM
0.5 PPM
<15 sec
3 Yrs
-4 to 122
-20 to 50
15 – 90%
Hydrogen Chloride
4101-21
EC
0-20
PPM
0.1 PPM
<100 sec
2 Yrs
-4 to 122
-20 to 50
15 – 90%
Hydrogen Cyanide
4101-22
EC
0-20
PPM
0.1 PPM
<70 sec
2 Yrs
-4 to 122
-20 to 50
15 – 90%
Ammonia
4101-25
EC
0-50
PPM
1.0 PPM
<30 sec
(5)
14 to 113
-10 to 45
20 – 95%
Hydrogen Fluoride
4101-26
EC
0-10
PPM
1.0 PPM
<30 sec
(5)
14 to 113
-10 to 45
20 – 95%
Ethylene Oxide
4101-27
EC
0-20
PPM
0.1 PPM
<90 sec
2 Yrs
-4 to 122
-20 to 50
15 – 90%
Notes:
(1) Response time to 90% full signal value for applied concentration
(2) Sensor life typical for use at standard temperature and pressure with occasional exposure to gas of interest
(3) Step to 50% LEL within 10 seconds.  Recovery to 10% LEL within 30 seconds
(4) Hydrogen tolerent
(5) Diffusion via membrane.  Requires electrolyte and membrane replacement every 6 months.
Construction
Modules
Dimensions
Weight
   4101-02
H: 7.5", D: 4.0", W: 4.0"
2.0 lb
(21.6 x 10.2 x 10.2 cm)
(0.9 Kg)
   4101-03EL
H: 8.5", D: 4.0", W: 4.0"
2.1 lb
(21.6 x 10.2 x 10.2 cm)
(1.0 Kg)
   4101-04-27 H: 8.0", D: 4.5", W: 4.0"
2.7 lb
(20.3 x 15.2 x 15.2 cm)
(1.3 Kg)
   4101-25/26 H: 10.2", D: 6.0", W: 6.0"
2.7 lb
(25.9 x 15.2 x 15.2 cm)
(1.3 Kg)
© 2004 by Sierra Monitor Corporation
05/04
4101-02 Combustible Gas Sensor
is FM Approved