United States Stove 2020L Benutzerhandbuch

Seite von 28
AIR FOR COMBUSTION AND VENTILATION 
CONTINUED
B.
Vent room directly to the outdoors.  See 
Ventilation Air from Outdoors, page 10.
C.
Install a lower BTU/Hr firebox, if lower BTU/Hr size makes room unconfined.
If the actual BTU/Hr used is less than the maximum BTU/Hr the space can support, the space
is an unconfined space.  You will need no additional fresh air ventilation.
WARNING
If the area in which the heater may be operated is smaller than that defined as an
unconfined space or if the building is of unusually tight construction, provide ad-
equate combustion and ventilation air by one of the methods described in the Na-
tional Fuel Gas Code, ANSI Z223.1, Section 5.3 or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space.  When ventilating to an ad-
joining unconfined space, you must provide two permanent openings: one within 12" of the
ceiling and one within 12" of the floor into adjoining room ( 
see options in Figure 1).
Follow the 
National Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for Combustion
and Ventilation for required size of ventilation grills or ducts.
WARNING
Rework worksheet, adding the space of the adjoining unconfined space.  The
combined spaces must have enough fresh air to supply all appliances in both
spaces.
Figure 1 - Ventilation Air from Inside Building
VENTILATION GRILLS INTO
ADJOINING ROOM.
OPTION 2
VENTILATION GRILLS
INTO ADJOINING
ROOM.
OPTION 1
OR REMOVE DOOR INTO
ADJOINING ROOM.
OPTION 3
9