Monessen Hearth WDV500 Benutzerhandbuch

Seite von 48
78D0011
15
WDV Series Gas Fireplace
VentInG InstallatIOn 
A  10’
B  7’
10’
FP2426
max vent run w/elbows
Figure 14 - 
Maximum Vent Run with Elbows
A + B = 17' Maximum
90° Elbow = 3'
FP2426
Example: 
Elbow 1   =   90°
 
Elbow 2   =   45°
 
Elbow 3   =   45°
 
Elbow 4   =   90°
Total Angular Variation  =   270°
Figure 15 - 
Maximum Elbow Usage 
1
2
3
4
1
2
3
4
FP1180
max bends
12" 
Minimum
FP1180
BelOW GraDe InstallatIOns
When it is not possible to meet the required vent terminal 
clearances of 12" above grade level, a snorkel kit is recom-
mended. It allows installation depth down to 7" (178 mm) 
below grade level. The 7" (178 mm) is measured from the 
center of the horizontal vent pipe as it penetrates through 
the wall.
ensure that sidewall venting clearances are observed. 
If venting system is installed below ground, we recom-
mend a window well with adequate and proper drainage 
to be installed around the termination area.
If installing a snorkel, a minimum 12" vertical rise is neces-
sary. The maximum horizontal run with the 12” vertical pipe 
is 36". This measurement is taken from the collar of the 
fireplace (or transition elbow) to the face of the exterior wall. 
See the Sidewall Venting Graph for extended horizontal 
run if the vertical exceeds 12".
1.  Establish vent hole through the wall.  
2.  Remove soil to a depth of approximately 16" below base 
of snorkel. Install drain pipe. Install window well (not 
supplied). Refill hole with 12" of coarse gravel leaving 
a clearance of approximately 4" below snorkel. Figure 
16
3.  Install vent system.
4.  Ensure a watertight seal is made around the vent pipe 
coming through the wall.
5.  Apply  high  temperature  sealant  caulking  (supplied) 
around the 5" and 8" snorkel collars.
6.  Slide the snorkel into the vent pipes and secure to the 
wall.
7.  Level the soil so as to maintain a 4" clearance below 
snorkel. Figure 16
FP2134
below grade install
FP2134
Figure 16 -  
Below Grade Installation
Screws
Minimum 
4" Clearance
Ground
Window 
Well 
Gravel 
Drain 
Foundation Wall 
Firestop 
12"
Minimum 
If  the  foundation  is  recessed,  use  recess  brackets  (not 
supplied) for securing lower portion of the snorkel. Fasten 
brackets to wall first, then secure to snorkel with self drill-
ing #8 x 1/2" sheet metal screws. It will be necessary to 
extend vent pipes out as far as the protruding wall face. 
Figure 17