Monessen Hearth WDV500 Benutzerhandbuch

Seite von 48
46
78D0011
WDV Series Gas Fireplace
requirements for the commonwealth of 
Massachusetts
This  product  must  be  installed  by  a  licensed  plumber  or 
gas  fitter  when  installed  within  the  Commonwealth  of 
Massachusetts.
note regarding Vented products
Flex  line  installation  must  not  exceed  36  inches  and  must 
have a T shutoff valve.
Any  residence  with  a  direct  vent  product  must  have  a  CO 
detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State 
of  Massachusetts  requires  the  damper  to  be  permanently 
removed or welded in the fully open position.
In addition, neither a naturally vented gas log nor a vent-free 
product may be installed in a bedroom or bathroom in the 
State of Massachusetts.
All gas fitting and installation of this heater shall only be done 
by a licensed gas fitter or licensed plumber.
For  all  side  wall  horizontally  vented  gas  fueled  equipment 
installed in every dwelling, building or structure used in whole 
or in part for residential purposes, including those owned or 
operated  by  the  Commonwealth  and  where  the  side  wall 
exhaust vent termination is less than seven (7) feet above 
finished grade in the area of the venting, including but not 
limited  to  decks  and  porches,  the  following  requirements 
shall be satisfied:
Installation of carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented 
gas fueled equipment, the installing plumber or gas fitter shall 
observe that a hard wired carbon monoxide detector with an 
alarm  is installed on each additional level of the dwelling, 
building  or  structure  served  by  the  side  wall  horizontal 
vented  gas  fueled  equipment.  It  shall  be  the  responsibility 
of  the  property  owner  to  secure  the  services  of  qualified 
licensed professionals for the installation of hard wired carbon 
monoxide detectors.
In the event that the side wall horizontally vented gas fueled 
equipment is installed in a crawl space or an attic, the hard 
wired carbon monoxide detector with alarm and battery back-
up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not 
be met at the time of completion of installation, the owner shall 
have a period of thirty (30) days to comply with the above 
requirements; provided, however, that during said thirty (30) 
day period, a battery operated carbon monoxide detector with 
an alarm shall be installed.
approved carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance 
with the above provisions shall comply with NFPA 720 and 
ANSI/UL 2034 listed and IAS certified.
signage
A  metal  or  plastic  identification  plate  shall  be  permanently 
mounted to the exterior of the building at a minimum height 
of eight (8) feet above grade directly in line with the exhaust 
vent terminal for the horizontally vented gas fueled heating 
appliance or equipment. The sign shall read, in print size no 
less than one-half (1/2) inch in size, “Gas Vent DIrectly 
BelOW, Keep clear OF all OBstructIOns”.
Inspection
The state or local gas inspector of the side wall horizontally 
vented gas fueled equipment shall not approve the installation 
unless,  upon  inspection,  the  inspector  observes  carbon 
monoxide detectors and signage installed in accordance with 
the provisions of 248 CMR 5.08(2)(a)1 through 4.
exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a)1 
through 4:
• 
The equipment listed in Chapter 10 entitled “Equipment 
Not Required To Be Vented” in the most current edition of 
NFPA 54 as adopted by the Board; and
• 
Product Approved side wall horizontally vented gas fueled 
equipment installed in a room or structure separate from 
the dwelling, building or structure used in whole or in part 
for residential purposes.
ManuFacturer requIreMents
Gas equipment Venting system provided
When  the  manufacturer  of  Product  Approved  side  wall 
horizontally vented gas equipment provides a venting system 
design or venting system components with the equipment, the 
instructions provided by the manufacturer for installation of 
the equipment and the venting system shall include:
• 
Detailed  instructions  for  the  installation  of  the  venting 
system design or the venting system components; and
• 
A  complete  parts  list  for  the  venting  system  design  or 
venting system.
Gas equipment Venting system nOt provided
When  the  manufacturer  of  a  Product Approved  side  wall 
horizontally vented gas fueled equipment does not provide 
the  parts  for  venting  the  flue  gases,  but  identifies  “special 
venting systems”, the following requirements shall be satisfied 
by the manufacturer:
• 
The referenced “special venting system” instructions shall 
be included with the appliance or equipment installation 
instructions; and
• 
The “special venting systems” shall be Product Approved 
by the Board, and the instructions for that system shall 
include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved 
side wall horizontally vented gas fueled equipment, all venting 
instructions, all parts lists for venting instructions, and/or all 
venting design instructions shall remain with the appliance or 
equipment at the completion of the installation.