Monessen Hearth 36CDVXTRN Benutzerhandbuch

Seite von 44
33
CDVX Series Direct Vent Gas Fireplace
20012253
WARNING:  BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT.
   
SYMPTOM 
  POSSIBLE CAUSES 
 
CORRECTIVE ACTION
1. Spark ignitor will not light 
A. Defective or misaligned  
Using a match, light pilot. If pilot lights, turn off    
   
 
  electrode at pilot. 
pilot and push the red button again.  If pilot will not  
   
 
   
light - check gap at electrode and pilot-should be  
   
 
   
1/8” to have a strong spark.
   
 
   
 
B.  Defective ignitor (Push Button) 
Push Piezo Ignitor Button. Check for spark at  
 
   
 
   
electrode and pilot. If no spark to pilot, and elec-   
   
 
   
trode wire is properly connected, replace ignitor.
2. Pilot will not stay lit after 
A.  Defective pilot generator 
Check pilot flame.  Must impinge on thermo- 
 
  carefully following lighting 
  (thermocouple), remote wall  
couple/thermopile.  Note: this pilot burner assem- 
  instructions. 
  switch. 
bly utilizes both-a thermocouple and a thermopile.   
   
 
   
The thermocouple operates the main valve  
 
   
 
   
operation (On and Off). Clean and or adjust pilot for  
   
 
   
maximum flame impingement on thermopile and   
   
 
   
thermocouple.
   
 
B. Defective automatic valve 
Turn valve knob to “Pilot”.  Maintain flow to pilot;   
   
 
   
millivolt meter should read greater than 10 mV.  If  
   
 
   
the reading is okay and the pilot does not stay on,  
   
 
   
replace the gas valve.  Note:  An interrupter block  
   
 
   
(not supplied) must be used to conduct this test.
3. Pilot burning, no gas to 
A. Wall switch or wires defective 
Check wall switch and wires for proper connec-   
  main burner 
   
tions. Jumper wire across terminals at wall  
 
   
 
   
switch, if burner comes on, replace defective wall  
   
 
   
switch. If okay, jumper wires across wall switch    
   
 
   
wires at valve, if burner comes on, wires are faulty  
   
 
   
or connections are bad.
   
 
B. Thermopile may not be 
1. Be sure wire connections from thermopile at    
   
 
  generating sufficient 
  gas valve terminals are tight and thermopile is fully  
   
 
  millivoltage. 
  inserted into pilot bracket.
   
 
   
2. One of the wall switch wires may be grounded.  
   
 
   
  Remove wall switch wires from valve terminals if  
   
 
   
  pilot now stays lit, trace wall switch wiring for    
   
 
   
  ground. May be grounded to fireplace or gas    
   
 
   
  supply.
   
 
   
3. Check thermopile with millivolt meter. Take  
 
   
 
   
  reading at thermopile terminals of gas valve.    
   
 
   
  Should read 250-300 millivolts (minimum 150)  
   
 
   
  while holding valve knob depressed in pilot    
   
 
   
  position and wall switch “Off”.  Replace faulty    
   
 
   
  thermopile if reading is below specified minimum.
   
 
   
 
C. Plugged burner orifice. 
Check burner orifices for debris and remove.
   
 
D. Defective automatic valve  
Turn valve knob to “On”, place wall switch to “On”  
   
 
  operator. 
millivolt meter should read greater than 100 mV.  If  
   
 
   
the reading is okay and the burner does not come  
   
 
   
on, replace the gas valve.
4. Frequent pilot outage 
A. Pilot flame may be too low 
Clean and/or adjust pilot flame for maximum flame 
  problem. 
  or blowing (high) causing the 
impingement on thermopile and thermocouple.
   
 
  pilot safety to drop out.
   
 
B. Possible blockage of the vent 
Check the vent terminal for blockage (recycling the  
   
 
  terminal. 
flue gases)
   
 
Troubleshooting the Gas Control System
NOTE:  Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.
SIT NOVA 820 MILLIVOLT VALVE