58D6002
Pipe Coupling
To Heater 
Valve
Gas Supply 
Inlet 
CONNECTING THE GAS
NOTICE: A  qualified  gas  appliance  installer  must  connect  the  heater  to  the  gas  supply.  Consult  all 
local codes.
IMPORTANT: 
Hold heater valve firmly with a wrench to prevent movement when connecting to inlet pipe. 
Manual Shutoff
Valve
Pipe
Stainless
Flexible Tube
Figure 9 - Gas Connection
Always use an external regulator for all propane/LPG heaters and high pressure one to two-pound systems only, to 
reduce the supply tank pressure to a maximum of 13" w.c. This is in addition to the internal regulator in the heater valve.
Locations that the Pressure 
Tapping Point May Be Installed 
Use new black iron or steel pipe. Internally tinned copper or copper tubing can be used 
per National Fuel Code, section 2.6.3, providing gas meets hydrogen sulfide limits, and 
where permitted by local codes. Gas piping system must be sized to provide minimum 
inlet pressure (Listed on Data Plate) at the maximum flow rate (BTU/Hr). Undue pressure 
loss will occur if the pipe is too small.
A manual shutoff valve must be installed upstream of the appliance. Union tee and 
plugged 
1
/
8
" NPT pressure tapping point should be installed upstream of the appliance. 
See Figure 9.
CAUTION 
CHECK GAS TYPE: The gas supply must be the same as stated on the heater’s rating 
plate. If the gas supply is different, DO NOT INSTALL THE HEATER. Contact your dealer 
for the correct model. 