9.13 Outside Combustion Air Supply
IMPORTANT: If the building has a slight negative 
pressure or corrosive contaminants, such as 
halogenated hydrocarbons, are present in the air, an 
outside combustion air supply to the heater is 
required. Seal all combustion air pipe joints.
For TF-120 4" (10 cm) single wall pipe or for
TF-160/200/250/300/350/380 5" (13 cm) single wall 
pipe, PVC pipe, aluminum flex duct, or equivalent 
may be used for outside air supply.
Use of optional outside combustion air is not 
recommended with unvented heaters.
The air supply duct may have to be insulated to 
prevent condensation on the outer surface. The 
outside air terminal must not be more than 1' (31 cm) 
above the vent terminal.
9.13.1 Length Requirements
Follow the constraints listed 
9.13.2 Vertical Outside Air Supply 
Minimum of
2’ (0.61 m)
Description
Part Number
Vent Cap 5" (13 cm)
90502301