VENTING INSTALLATION 
INSTRUCTIONS
 WARNING: Read all instruc-
tions completely and thoroughly 
before  attempting  installation. 
Failure to do so could result in 
serious injury, property damage 
or loss of life. 
 WARNING: Seal all connec-
tions  with  high  temperature 
silicone every time a vent con-
nection is made. Before joining 
elbows  or  pipes,  apply  a  bead 
of  high  temperature  silicone 
sealant  to  the  male  end  of  the 
elbow or pipe. High temperature 
silicone must also be used to re-
seal any connections after main-
tenance to venting system.
NOTICE: Failure to follow these in-
structions will void the warranty. 
NOTICE: Do not seal termination 
cap to vent pipe. Cap must be 
removable  for  vent  inspection 
and maintenance.
INSTALLATION PRECAUTIONS
Consult local building codes before beginning the 
installation. The installer must make sure to select 
the proper vent system for installation. Before 
installing vent kit, the installer must read this 
fireplace manual and vent kit instructions.
Only a qualified service person should install 
venting system. The installer must follow these 
safety rules:
•  Wear gloves and safety glasses for protection
•  Use extreme caution when using ladders or 
when on roof tops
•  Be aware of electrical wiring locations in walls 
and ceilings
The following actions will void the warranty on 
your venting system:
•  Installation of any damaged venting component
•  Unauthorized modification of the venting system
•  Installation of any component part not manu-
factured or approved by DESA 
•  Installation other than as instructed by these 
instructions
 WARNING: This gas fireplace 
and  vent  assembly  must  be 
vented directly to the outside. The 
venting system must NEVER be 
attached to a chimney serving a 
separate solid fuel burning appli-
ance. Each gas appliance must 
use a separate vent system. Do 
not use common vent systems.
  WARNING:  Horizontal  sec-
tions of this vent system require 
a minimum clearance of 2" from 
the top of the pipe and 1" mini-
mum to the sides and bottom. 
Vertical sections of this system 
require a minimum of 1" clear-
ance  to  combustible  materials 
on all sides of the pipe.
INSTALLATION PLANNING
There are two basic types of direct-vent installation:
•  Horizontal Termination 
•  Vertical Termination 
It is important to select the proper length of vent 
pipe for the type of termination you choose. It is 
also important to note the wall thickness. 
For Horizontal Termination:
 Select the amount 
of vertical rise desired. The horizontal run of 
venting must have 1/4" rise for every 12" of run 
towards the termination.  
  WARNING:  Never  run  the 
vent  downward  as  this  may 
cause excessive temperatures 
which could cause a fire.
You may use one or two 90° elbows in this vent 
configuration. See Horizontal Termination Con-
figurations on page 15.