Carrier 38AQS008 Benutzerhandbuch

Seite von 20
UNIT
38AQS008
UNIT
W/ALUMINUM COIL
UNIT
W/COPPER COIL
WEIGHT CHART (WITH ALUMINUM COIL)
WEIGHT CHART (WITH COPPER COIL)
Std Unit Corner W Corner X Corner Y Corner Z Std Unit Corner W Corner X Corner Y Corner Z
Dim. A
Dim. B
Dim. A
Dim. B
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
60 Hz
1
⬘-8⬙
[508.0]
1
⬘-5⬙
[431.8]
1
⬘-9
1
2
[546.0]
1
⬘-4
3
4
[425]
540 245 132
60
100
45
133
60
175
80 608 276 160
73
117
53
142
64
189
86
50 Hz
1
⬘-6⬙
[457.2]
1
⬘-7⬙
[482.6]
1
⬘-7
1
2
[495.3]
1
⬘-6
3
4
[476.3]
594 270 114
52
114
52
183
83
183
83 662 299 142
64
131
59
192
87
197
89
NOTES:
1. Dimensions in [
] are in millimeters.
2.
Center of Gravity. See chart for dimensions.
3.
Direction of airflow.
4. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces, 0 in. (0 mm)
b. Outdoor coil, for proper airflow, 36 in. (914 mm) one side, 12 in.
(305 mm) the other. The side getting the greater clearance is optional.
c. Overhead, 60 in. (1524 mm) to assure proper outdoor-fan operation.
d. Between units, control box side, 42 in. (1067 mm) per National
Electrical Code (NEC, U.S.A.).
e. Between unit and ungrounded surfaces, control box side, 36 in.
(914 mm) per NEC (U.S.A.).
f. Between unit and block or concrete walls and other grounded surfaces,
control box side, 42 in. (1067 mm) per NEC (U.S.A.).
5. With the exception of the clearance for the outdoor coil as stated in
note 4b, a removable fence or barricade requires no clearance.
6. Units may be installed on combustible floors made from wood or Class A,
B, or C roof covering material.
7. Vertical center of gravity is approximately 40% of total unit height.
ELECTRICAL CONNECTIONS
CONNECTION SIZES
AA
1
3
8
⬙ Dia. [35] Field Power Supply Hole
BB
2
⬙ Dia. [51] Power Supply Knock-Out
CC
2
1
2
⬙ Dia. [64] Power Supply Knock-Out
DD
7
8
⬙ Dia. [22] Field Control Wiring Hole
SERVICE VALVE CONNECTIONS
UNIT
SUCTION
LIQUID
38AQS008
1
1
8
⬙ [28.6]
1
2
⬙ [12.7]
Fig. 2 — Dimensions
4