Fan speed is switched according to the number of operating indoor unit and the compressor frequency.
Note
• When the indoor coil thermistor is 134.6˚F or more on HEAT operation, fan speed is fixed to Low speed.
• When the indoor coil thermistor is 134.6˚F or more on HEAT operation, fan speed is fixed to Low speed.
Or, the indoor coil thermistor is 113˚F or less on HEAT operation, fan speed is back to normal.
3-4. HEAT DEFROSTING CONTROL
(1) Conditions to enter defrosting mode
1
. When temperature of defrosting thermistor is 26.6˚F or less.
2
. When specified non-defrosting time, is counted in the control p.c. board is satisfied.
(Total time of compressor operating)
Going to defrosting mode at both condition of
Going to defrosting mode at both condition of
1
and
2
.
(2) Defrosting operation
1
. Compressor stops for 50 seconds, Indoor fan is off, Defrosting lamp lights.
2
. 4-way valve reverses flow, Compressor operates by the frequency in heat defrosting control.
3
. After compressor stops for 35 seconds, 4-way valve reverses flow, then defrosting finishes.
(3) Conditions to finish defrosting mode
1
. When the defrosting thermistor temperature is 55.76˚F or more.
2
. When it has spent 10 minutes for defrosting.
Defrosting finishes at condition of
1
or
2
.
This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge
temperature thermistor.
(1) Compressor ON/OFF
temperature thermistor.
(1) Compressor ON/OFF
When temperature of the discharge temperature thermistor exceeds 240.8˚F, the control stops the compressor.
When temperature of the discharge temperature thermistor is 176˚F or less, the controls starts the compressor.
When temperature of the discharge temperature thermistor is 176˚F or less, the controls starts the compressor.
(2) Compressor operation frequency
When temperature of the discharge temperature thermistor is expected to be higher than 240.8˚F, the control decreases 12Hz
from the current frequency.
When temperature of the discharge temperature thermistor is expected to be higher than 231.8˚F and less than 240.8˚F, the
control decreases 6Hz from the current frequency.
When temperature of the discharge temperature thermistor is expected to be higher than 219.2˚F and less than 231.8˚F, the
control is set at the current frequency.
from the current frequency.
When temperature of the discharge temperature thermistor is expected to be higher than 231.8˚F and less than 240.8˚F, the
control decreases 6Hz from the current frequency.
When temperature of the discharge temperature thermistor is expected to be higher than 219.2˚F and less than 231.8˚F, the
control is set at the current frequency.
3-5. DISCHARGE TEMPERATURE PROTECTION CONTROL
3-6. OUTDOOR FAN CONTROL
COOL
Fan speed
Up
Down
Up
Down
Mode
HEAT
Compressor frequency
<Relation between compressor frequency and fan speed.>
40Hz
30Hz
40Hz
30Hz
Up
Down
Fan speed
High
Low
Compressor frequency
Min.
Max.