HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
66-2069—02
8
 
Fig. 6. ASSY786 Viewing Head Plug Assembly with C330S.
Protecting the Viewing Head Cable 
(Connector Series)
Note that when the wiring needs to meet Class I, Division 2 
requirements for use in hazardous locations and when conduit 
is used, the conduit must be sealed where the cable passes 
from the hazardous location to the non-hazardous location in 
order to keep potentially hazardous gases from being 
conducted into the non-hazardous area.
Viewing Head Connector LED 
Indicators
The viewing head connector has orange and green LEDs 
which can be viewed from the rear of the connector when the 
connector cover is removed. 
The green LED displays the pulses out of the viewing head 
and the orange LED shows that the self-checking signal from 
the signal processor is reaching the viewing head. If power is 
on at the signal processor, the orange LED should flash at one 
pulse per second, even if the viewing head is not plugged in. 
This is helpful in troubleshooting. 
With no flame signal present, the green LED will flash one 
pulse per second in step with the self-checking signal. The 
viewing head is sending back an ID pulse; this is part of the 
self-checking system. When a flame is present, the green 
LED will flash at a rate proportional to the flame signal, except 
when the pulses are interrupted once per second for the self-
check pulse arrival at the viewing head. The pulse rate of the 
green LED flashes can be used for aiming the viewing head.
NOTE: The LED indicators are provided for alignment 
and troubleshooting only. Reinstall cover with 
gasket correctly in place at all times, and ensure 
that connector coupling is tightened securely. 
This gasket and cover must be installed properly 
to maintain NEMA rating. 
Viewing Head Mounting and Sighting
Mounting is 1/2-in. NPT (F) for all viewing head models with a 
1/4-in. NPT (F) purge air connection. Before beginning 
installation, determine the best location for mounting the 
viewing head based upon the following factors:
Viewing Head Mounting Block
The S70X viewing heads are held firmly in place in their 
mounting blocks by two galvanized steel latches. The S80X 
viewing head is secured in its mounting block by a friction 
twist-lock. Refer to the ACCESSORIES section for part 
numbers.
Pressure
The S70X viewing head lens will withstand 50 psi (3.4 bar) 
while the S80X lens will withstand 90 psi (6.2 bar), provided 
the compression ring on the purge air adapter is tightened 
properly. If the lens assembly is exposed to greater pressures 
through the sight pipe, then an isolation unit must be used. 
Honeywell isolation units with purge air entrance are available 
as accessories; ISO-UNIT, ISO-UNITSS, ISO-UNITHPGT. 
Each has a quartz window, two 1-in. NPTF connections and a 
1/2-in. NPTF purge port.
Temperature
The case temperature of the viewing head housing must not 
exceed 185°F (85°C) while the standard Delrin mounting 
block must not exceed 180°F (82°C) continuous service. Care 
should be taken to ensure the case housing and mounting 
block temperatures do not exceed these values.
Purge air will help reduce conducted heat through the sight 
pipe and flange. A heat insulating Ultem replacement viewing 
head mounting block is available for both the S70X/S80X 
models (part numbers 700UA and 800UA) with a continuous 
service rating of 320°F (160°C) as well a 1/2-in. NPTM Ultem 
nipple (part number R-518-13) or an Ultem locking coupler 
adapter (R-518-PT13 or R-518-PT13L) to reduce the 
conducted heat, but direct radiation can cause the housing 
case temperature to exceed limits. If the ambient heat (direct 
radiation) is excessive, then an air cooling canister with vortex 
cooler should be considered or alternately a fiber optic 
extension. The extension uses a fiber optic cable assembly 
between the sight pipe and the viewing head, allowing the 
viewing head to be placed further away from the heat source. 
Refer to the Fiber Optic Manual 69-2683 or contact your 
distributor or the factory for assistance with fiber optic 
selection and pricing.
Purge Air
Use a flexible air supply line, to allow for repositioning of the 
viewing head and sight pipe until a final and permanent 
M35140