Goodman Mfg SS-CPC90-150 Benutzerhandbuch

Seite von 36
p
rodUCt
 s
peCifiCations
p
rodUCt
 s
peCifiCations
SS-CPC90-150
  
www.goodmanmfg.com 
11
h
eat
 k
it
 e
leCtriCal
 d
ata
 (B
lower
 o
nly
, h
eat
 m
ode
)
 — 7½ t
ons
 (a m
odles
)
m
inimUm
 a
irflow
 
for
 e
leCtriC
 h
eat
Heater Size (kW)
Minimum CFM
15
3,000
30
3,000
43
3,000
kw C
orreCtion
 f
aCtors
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
230
220
210
208
Correction Factor
1
0.93
0.82
0.78
0.76
kW Correction Factor (for 480V Units)
Supply Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
For other voltage, use voltage² / 480²
kW Correction Factor (for 575V Units)
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.
Model and 
Heat Kit Usage
MCA¹ 
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC090XXX3BXXX
40
50
EHK3-16
48 / 55
50 / 60
15
3000 - 3375 CFM
EHK3-30
87 / 100
90 / 100
30
3000 - 3375 CFM
EHK3-45
121 / 139
125 / 150
43
3000 - 3375 CFM
Model and 
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
Recommended
Airflow Range
CPC090XXX4BXXX
19
25
EHK4-16
27
30
15
3000 - 3375 CFM
EHK4-30
50
50
30
3000 - 3375 CFM
EHK4-45
70
70
43
3000 - 3375 CFM
Model and 
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
Recommended
Airflow Range
CPC090XXX7BXXX
14
15
EHK7-16
22
25
15
---
EHK7-30
41
45
30
---
EHK7-45
57
60
43
---
¹   Minimum Circuit Ampacity