Maintain an adequate clearance around the unit for safety, service, maintenance, 
and proper unit operation. Leave a total clearance of 75” on the main control 
panel side of the unit for possible removal of fan shaft, coil, electric heat, and  
gas furnace. Leave a clearance of 48” on all other sides of the unit for possible 
compressor removal or service access, and to ensure proper ventilation  
and condenser airflow. Do not install the unit beneath any obstruct- 
ion. Install the unit away from all building exhausts to inhibit  
ingestion of exhaust air into the unit’s fresh-air intake.