SS-DSZC18
www.goodmanmfg.com
3
S
peCifiCationS
DSZC18
0361A
DSZC18
0481A
DSZC18
0601A
DSZC18
0601B
Cooling Capacity
Nominal Cooling (BTU/h)
Nominal Cooling (BTU/h)
35,000
47,000
57,000
57,000
Nominal Heating (BTU/h)
35,000
47,000
57,000
57,000
Decibels
72
73
75
75
Compressor
RLA
RLA
16.7
21.2
25.6
23.0
LRA
82
96
118
118
Condenser Fan Motor
Horsepower (RPM)
Horsepower (RPM)
⅓
⅓
⅓
⅓
FLA
2.8
2.8
2.8
2.8
Refrigeration System
Refrigerant Line Size¹
Refrigerant Line Size¹
Liquid Line Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
Suction Line Size (“O.D.)
⅞"
1⅛"
1⅛"
1⅛"
Refrigerant Connection Size
Liquid Valve Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
Suction Valve Size (“O.D.)
⅞"
1⅛"
1⅛"
1⅛"
Valve Connection Type
Sweat
Sweat
Sweat
Sweat
Refrigerant Charge
188
278
278
278
Expansion Device
TXV
TXV
TXV
TXV
Superheat at Service Valve
7-9°F
7-9°F
7-9°F
7-9°F
Subcooling at Service Valve
High Stage
8-10°F
8-10°F
8-10°F
8-10°F
Low Stage
5-7°F
5-7°F
5-7°F
5-7°F
Electrical Data
Voltage-Phase-Hz
Voltage-Phase-Hz
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
Minimum Circuit Ampacity ²
23.7
29.3
34.8
31.6
Max. Overcurrent Protection ³
40
50
60
50
Min / Max Volts
197 / 253
197 / 253
197 / 253
197 / 253
Electrical Conduit Size
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
Ship Weight (lbs)
293
340
360
360
¹ Tested and rated in accordance with ARI Standard 210/240
² Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
² Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the rating plate for electrical data on the unit being installed.
• Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
• Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT,
• Always check the rating plate for electrical data on the unit being installed.
• Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
• Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT,
NOT THE INDOOR COIL.