1. Make sure the chassis is level. Check by pouring water 
into the drain pan and making certain it flows through 
the drain hoses to the condenser side of the unit.
2. Plug or hard wire line voltage to unit.
IMPORTANT: Follow the information provided on the rat-
ing  plate  for  voltage  and  amperage/fuse  size  for  proper 
supply.
3. Attach  the  front  panel  to  the  existing  cabinet  enclo-
sure.
4. Turn the power on.
5. Check for proper operation (i.e., cooling, optional fresh 
air, and heating if supplied).
6. Check to be sure nothing will interfere with the room 
UNIT MOUNTED THERMOSTAT 
OPERATIONAL INSTRUCTIONS
Turning the unit mounted thermostat knob to the far left 
will produce the warmest room temperature while turning 
it all the way to the right will produce the coolest.  These 
settings can be adjusted for personal comfort.
RC12 SAFETY NOTE: When turning the selector switch on 
the RC12 for mode of operation, it is very important to make 
sure the switch position is 
SEATED” directly on a mode of 
operation (clicks into position)Do not mistakenly place 
between two positions. This can result in a potential fan 
failure while the system is in a cooling or heating operation. 
A fan failure could result in the unit overheating (smoke) in 
an electric heating mode, or freezing coil in a cooling mode.
COOLING CYCLE:
1. Place system switch in the “COOL” position.
2. Rotate thermostat knob (below) clockwise until the com-
pressor fans start running and cold air begins to flow 
from the unit. For a colder room temperature, continue 
turning the thermostat knob clockwise and let the unit 
continue operating to cool the room and remove humid-
ity. If a warmer room temperature is desired, rotate the 
thermostat knob counter-clockwise until the compressor 
cycles off.
FINAL INSPECTION AND STARTUP
SEQUENCE OF OPERATION
Avoid rotating the thermostat knob back and forth from 
heating to cooling. This causes the compressor to cycle 
on and off rapidly and WILL cause damage to the com-
pressor. Allow the compressor to remain off for at least 
three minutes prior to restarting the unit.
!  
!  
CAUTION
 
When the unit is first powered up, high humidity condi-
tions can cause condensation to form on the discharge 
grill. Keep doors and windows closed to reduce humidity 
and condensation will evaporate.
!  
!  
CAUTION
discharge air or the return air to the units (i.e., curtains 
or drapes that obstruct the air flow or plush carpeting 
that can obstruct the return air (see below)). Items like 
these can cause serious damage to the chassis and 
can void the warranty.
Typical Representation Of A Unit Mount Control
NOTE:  RetroAire  units  can  be  equipped  with  Unit 
Mounted or Remote Controlled Thermostats. 
NOTE: Any  obstruction  of  supply  air 
including the use of deflector baffles, 
may cause condensate to form on the 
louver or cabinet.
To  ensure  optimum  performance  of  your  PTAC, 
avoid restricting the air flow.
The  position  of  curtains  or  drapes 
over supply air grille may cause air to 
recirculate  without  cooling  the  room. 
The unit will short cycle and may cause 
premature compressor failure.