Friedrich SH15L30-B Benutzerhandbuch

Seite von 16
4
COMPRESSOR WINDING TEST (Figure 2.)
Remove the compressor terminal box cover and disconnect the 
wires from the terminals. Using an ohmmeter, check continuity 
across the following:
COMPONENT OPERATION AND TESTING
COMPRESSORS
Compressors are single phase, 208/230 volt. All compressor 
motors are permanent split capacitor type, using only a running 
capacitor across the start and run terminal.
All compressors are internally spring mounted and externally 
mounted on rubber isolators.
Line Voltage Overload
The compressor is equipped with an internal line voltage over-
load. This overload is embedded in the windings of the motor 
to sense the motor temperature. The overload will open and 
disconnect the power to the motor due to high temperatures 
caused by:
1.  A locked rotor.
2.  Excessive running amps.
3.  High discharge temperature.
4.  Low refrigerant charge.
FIGURE 1  INTERNAL OVERLOAD
LINE BREAK 
INTERNAL OVERLOAD
OHMMETER
FIGURE 2 COMPRESSOR WINDING TEST
Testing Procedures
1. 
Terminal "C" and "S" – no continuity – open winding 
– replace compressor.
2.  Terminal "C" and "R" – no continuity – open winding 
– replace compressor.
3.  Terminal "R" and "S" – no continuity – open winding 
- replace compressor.
4. 
Terminal "C" and the shell of the compressor – continuity 
– grounded motor – replace compressor.
5.  Should continuity exist between terminals "R" and "S", 
but not between terminals "C" and "S" and "C" and "R", 
the internal overload may be open. If the compressor is 
extremely hot, allow it suffi cient time to cool. It may require 
as long as one hour for the compressor to cool suffi ciently 
for the internal overload to close.
CHECKING COMPRESSOR EFFICIENCY
The reason for compressor ineffi ciency is normally due to bro-
ken or damaged suction and/or discharge valves, reducing the 
ability of the compressor to pump refrigerant gas.
This condition can be checked as follows:
1.  Install a piercing valve on the suction and discharge or liquid 
process tube.
2.  Attach gages to the high and low sides of the system.
3.  Start the system. Run a "cooling or heating performance test."
If test shows:
A.  Below normal high side pressure. 
B.  Above normal low side pressure.
C.  Low temperature difference across the coil.
The compressor valves are faulty - replace the compressor.
GROUND TEST
Use an ohmmeter set on its highest scale. Touch one lead to 
the compressor body (clean point of contact, as a good connec-
tion is a must) and the other probe in turn to each compressor 
terminal. (See Figure 3.) If a reading is obtained, the compressor 
is grounded and must be replaced.
FIGURE 3 TYPICAL GROUND TEST
WARNING
DISCONNECT ELECTRICAL POWER TO THE 
UNIT BEFORE SERVICING OR TESTING