Friedrich CP14 Benutzerhandbuch

Seite von 16
15
Air conditioner power supply cord trips (Reset button 
pops out)
Disturbances in your electrical current can trip (Reset 
button will pop out) the power supply cord.
 Press and 
release RESET (listen for click; Reset button will latch and 
remain in) to resume operation.
Electrical overloading, overheating, cord pinching or 
aging can trip (Reset button will pop out) the power 
supply cord.
 After correcting the problem, press and release 
RESET (listen for click; Reset button will latch and remain in) 
to resume operation.
NOTE: A damaged power supply cord must be replaced with a 
new power supply cord obtained from the product manufacturer 
and must not be repaired.
Air conditioner seems to run too much
The current air conditioner replaced an older model. The 
use of more efficient components may cause the air 
conditioner to run longer than an older model, but the total 
energy consumption will be less. Newer air conditioners do 
not emit the “blast” of cold air you may be accustomed to 
from older units, but this is not an indication of lesser cooling 
capacity or efficiency. Refer to the efficiency rating (EER) and 
capacity rating (in BTU/hr.) marked on the air conditioner.
The air conditioner is in a heavily occupied room, or heat-
producing appliances are in use in the room. 
Use exhaust 
vent fans while cooking or bathing and try not to use heat-
producing appliances during the hottest part of the day. A 
higher capacity air conditioner may be required, depending 
on the size of the room being cooled.
Air conditioner cycles on and off too much, or does not 
cool/heat room in cooling/heating mode
The Mode or Fan control is set to Power Saver (on some 
models). 
Use Power Saver only when you are asleep or away 
from home, since the fan does not circulate the room air 
continuously. Use Low Cool, Medium Cool or High Cool for 
your best comfort.
The air conditioner is not properly sized for your room.
Check the cooling capabilities of your room air conditioner. 
Room air conditioners are not designed to cool multiple 
rooms. 
The filter is dirty or obstructed by debris. Clean the filter. 
The inside evaporator and outside condenser coils are 
dirty or obstructed by debris.
 See “Annual Maintenance.”
There is excessive heat or moisture (open container 
cooking, showers, etc.) in the room.
 Use a fan to exhaust 
heat or moisture from the room. Try not to use heat-
producing appliances during the hottest part of the day.
The louvers are blocked. Install the air conditioner in a 
location where the louvers are free from curtains, blinds, 
furniture, etc.
The outside temperature is below 65°F (18°C). Do not try to 
operate your air conditioner in the cooling mode when the 
outside temperature is below 65°F (18°C).
The temperature of the room you are trying to cool is 
extremely hot. 
Allow extra time for the air conditioner to cool 
off a very hot room.
Windows or doors to the outside are open. Close all 
windows and doors.
The Vent control is set to OPEN (on some models). Push 
the Vent control to CLOSED for maximum cooling and/or 
heating.
The temperature set point or Thermostat control is not at 
a cool enough setting.
 Adjust the temperature set point to a 
cooler setting by pressing the minus button to reduce the 
temperature or adjust the Thermostat control to a cooler 
setting by turning the knob clockwise. Turn the Fan control to 
Turbo Cool.
The air contitioner in the heating mode has insufficient 
BTU/hr for the heating requirements of the room. 
Do not 
use the air conditioner as a primary source of heat.
Temperature on display does not match room 
temperature
When the compressor and fan motor turn off during 
Power Saver mode, or after you turn off the unit, a lower 
temperature reading than the actual room temperature 
may be displayed for a short period of time.
 This lower 
temperature reading is caused by the temperature sensor 
being located close to the cold evaporator coil. The actual 
room temperature will display within a few minutes.
Water drips from cabinet into your house
The air conditioner is not properly leveled. The air 
conditioner should slope slightly downward toward the 
outside. Level the air conditioner to provide a downward 
slope toward the outside to ensure proper drainage. See the 
Installation Instructions. 
NOTE: Do not drill a hole into the bottom of the metal base 
and condensate pan.
Assistance or Service
For further assistance
If you need further assistance, you can write to ask any questions
or tell us about your concerns to:
Friedrich Air Conditioning Co.
P.O. Box 1540
San Antonio, TX   78295-1540
For assistance, service or replacement parts
For service assistance or to locate factory-authorized parts,
call our Customer Service Center at 210-357-4400, or your
nearest authorized service center. You also can visit the "Dealer
Locator" at 
www.friedrich.com to locate your nearest authorized
Friedrich Service Center.
Customer Assurance
Or email: tac@friedrich.com
Please include a daytime phone number in your 
correspondence.