DUCTWORK 
When installing ductwork, adhere to local Codes and 
sensible practice. Minimize duct runs and avoid abrupt 
changes in direction where possible. Allow ample access 
space for servicing of the coils and changing of filters. 
Perform regular maintenance on ducts to increase unit 
life, maintain efficient operation, and reduce accumu-
lation of explosive dust. Refer to blower performance 
charts,  and  engineer  duct  runs  and  accessory  pres-
sure drop so as not to exceed maximum external static 
values. 
LOUVER SIZING GUIDELINES 
One of the key issues in obtaining optimum performance 
from indoor air-conditioners is the proper selection of the 
condenser intake and discharge louvers. Unlike outdoor 
air cooled units, which intake and discharge their cooling 
virtually unrestricted, indoor units must overcome the 
resistance of grilles or louvers at the outside wall - plus 
the restriction of any interconnecting ductwork. 
Our indoor air cooled air-conditioners are designed to ac-
commodate the external static pressure loss associated 
with properly sized louvers of the “storm proof” type. This 
type of louver typically has a free area approximately 
40-45% of the actual louver size. To determine the free 
area required for any given unit, adhere to the following 
guidelines: 
-   Size condenser air intakes for 500-750 feet/minute 
nominal velocity 
    (Maximum recommended 800 feet/minute)
-   Size condenser air discharge for 1,200-1,500 feet/
minute nominal velocity
    (Maximum recommended 1,700 feet/minute) 
The use of louvers with higher velocities than above may 
be employed, at the discretion of the engineer/installer, 
provided that the total air pressure drop does not exceed 
the capability of the condenser fan and motor. The use 
of low restriction louvers with shallow blade angles can 
allow  higher  face  velocities  without  excessive  static 
pressure loss. 
Exceeding  the  static  pressure  capability  of  the  con-
denser fan will result in insufficient condenser air volume. 
This will cause a loss in system capacity, and may cause 
compressor shutdown during high ambient periods. (In-
stallation of an oversize condenser motor/drive, where 
applicable, may be considered in such cases.) 
(As a general rule, these velocities will require an intake 
louver sized approximately 1.25 to 1.5 times the dimen-
sions of the duct connection on the unit, and a discharge 
louver sized approximately 1.5 to 2 times the duct con-
nection dimensions.)  
Use only louver sections that provide different deflection 
angles for air discharge and air intake, to ensure the 
unit does not short circuit. Protect the unit from weather 
conditions (rain, snow) entering through the condenser 
air intake. All outdoor air ducts should pitch away from 
the unit, toward the outside wall. Connect all ducts to unit 
with canvas section duct connectors or choose another 
suitable noise and vibration absorbing device. 