Concealed Duct High Static Pressure
Installation Manual
EN
 : The air conditioner automatically enters the auto-address setting mode.
L20
LAN communication error
Network 
adapter central 
control
Address setting, central control remote controller, network adapter --- 
Duplication of address in central control communication
Auto-reset
L29
Other outdoor unit error
Outdoor
Other outdoor unit error
Entire stop
1) Communication error between IPDU MCU and CDB MCU
Entire stop
2) Abnormal temperature was detected by the heat sink temp. sensor 
in IGBT.
L30
Abnormal external input into 
indoor unit (interlock)
Indoor
External devices, outdoor unit P.C. board --- Abnormal stop due to 
incorrect external input into CN80
Entire stop
L31
Phase sequence error, etc.
Outdoor
Power supply phase sequence, outdoor unit P.C. board --- Abnormal 
phase sequence of the 3-phase power supply
Operation 
continued 
(thermostat 
OFF) 
P01
Indoor unit fan error
Indoor
Indoor fan motor, indoor P.C. board --- Indoor AC fan error (fan motor 
thermal relay activated) was detected.
Entire stop
P03
Outdoor unit discharge temp. 
error
Outdoor
An error was detected in the discharge temp. releasing control.
Entire stop
P04
Outdoor unit high-pressure 
system error
Outdoor
High-pressure switch --- The IOL was activated or an error was 
detected in the high-pressure releasing control using the TE.
Entire stop
P05
Open phase detected
Outdoor
The power supply wire may be connected incorrectly. Check open 
phase and voltages of the power supply.
Entire stop
P07
Heat sink overheat
Outdoor
Abnormal temperature was detected by the temp. sensor of the IGBT 
heat sink.
Entire stop
P10
Indoor unit water overflow 
detected
Indoor
Drain pipe, clogging of drainage, float switch circuit, indoor P.C. board 
--- Drainage is out of order or the float switch was activated.
Entire stop
P15
Gas leakage detected
Outdoor
There may be gas leakage from the pipe or connecting part. Check for 
gas leakage.
Entire stop
P19
4-way valve error
Outdoor
(Indoor)
4-way valve, indoor temp. sensors (TC/TCJ) --- An error was detected 
due to temperature drop of the indoor unit heat exchanger sensor 
when heating.
Auto-reset
(Auto-reset)
P20
High-pressure protective 
operation 
Outdoor
High-pressure protection
Entire stop
P22
Outdoor unit fan error
Outdoor
Outdoor unit fan motor, outdoor unit P.C. board --- An error 
(overcurrent, locking, etc.) was detected in the outdoor unit fan drive 
circuit.
Entire stop
P26
Outdoor unit inverter Idc 
activated
Outdoor
IGBT, outdoor unit P.C. board, inverter wiring, compressor --- Short-
circuit protection for compressor drive circuit devices (G-Tr/IGBT) was 
activated.
Entire stop
P29
Outdoor unit position error
Outdoor
Outdoor unit P.C. board, high-pressure switch --- Compressor motor 
position error was detected.
Entire stop
P31
Other indoor unit error
Indoor
Another indoor unit in the group is raising an alarm.
Entire stop
E03/L07/L03/L08 alarm check locations and error description
Auto-reset
Wired remote 
controller 
display
Main defective parts
Judging device
Parts to be checked / error description
Air conditioner 
status
Indication
40-EN