York R-410A ZH/ZJ/ZR Series Benutzerhandbuch

Seite von 206
528150-YTG-G-1210
Johnson Controls Unitary Products
25
1. 1
st
 Stage Capacity is 75% of Full Capacity.
2. 1
st
 Stage Capacity is 70% of Full Capacity.
3. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
4. 2 In. Pleated, Optional, MERV 7.
5. 4 In. Pleated, Optional, MERV 13.
CONDENSER FAN DATA
Quantity of fans
1
2
2
Fan diameter (Inch)
24
24
24
Type
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Quantity of motors
1
2
2
Motor HP each
1/3
1/3
1/3
No. speeds
 1
 1
 1
RPM
850
850
850
Nominal total CFM
3300
5500
6300
BELT DRIVE EVAP FAN DATA
Quantity
1
1
1
Fan Size (Inch)
12 x 9
12 x 9
12 x 9
Type
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VM34
1VL44
1VM34
1VL44
1VL40
1VP56
Blower Sheave
AK69
AK69
AK56
AK56
AK61
AK74
Belt
A47
A47
A47
A47
A47
A51
Motor HP each
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
RPM
1725
1725
1725
1725
1725
1725
Frame size
56
56
56
56
56
56
FILTERS
Quantity - Size
4 - (24 x 16 x 2)
3,4
4 - (24 x 16 x 2)
3,4
4 - (24 x 16 x 2)
3,4
4 - (24 x 16 x 4)
5
4 - (24 x 16 x 4)
5
4 - (24 x 16 x 4)
5
ZJ037-061 Two Stage Gas Heat Physical Data (Continued)
Component
Models
ZJ037
ZJ049
ZJ061
Nominal Tonnage
3.0
4.0
5.0