York R-410A ZH/ZJ/ZR Series Benutzerhandbuch

Seite von 206
528150-YTG-G-1210
36
Johnson Controls Unitary Products
115°F
125°F
750
77
36.4
3.3
13.7
12.3
9.1
-
-
-
32.6
3.5
12.4
10.7
8.1
-
-
-
72
31.9
3.2
19.7
16.6
13.4
10.3
-
-
28.4
3.4
18.2
15.2
12.2
9.1
-
-
67
27.4
3.1
25.8
20.9
17.7
14.6
11.4
-
24.1
3.4
24.1
19.3
16.3
13.2
10.2
-
62
24.2
3.0
24.2
24.2
21.7
18.6
15.4
12.3
21.4
3.2
21.4
21.4
21.4
17.2
14.1
11.1
900
77
37.2
3.3
17.4
13.8
10.1
-
-
-
33.1
3.6
16.7
12.5
8.9
-
-
-
72
32.6
3.2
22.2
18.5
14.8
11.1
-
-
28.8
3.5
20.6
17.0
13.4
9.8
-
-
67
28.0
3.2
26.9
23.2
19.5
15.8
12.1
-
24.5
3.4
24.5
21.5
17.9
14.4
10.8
-
62
24.7
3.1
24.7
24.7
23.9
20.2
16.5
12.8
21.7
3.3
21.7
21.7
21.7
18.7
15.1
11.5
57
25.4
3.1
25.4
25.4
24.0
20.3
16.6
12.9
22.7
3.3
22.7
22.7
22.0
18.4
14.8
11.3
1050
77
37.9
3.3
21.2
15.2
11.0
-
-
-
33.7
3.6
20.9
14.2
9.7
-
-
-
72
33.2
3.2
24.6
20.4
16.2
11.9
-
-
29.2
3.5
22.9
18.8
14.7
10.6
-
-
67
28.6
3.2
28.0
25.6
21.3
17.1
12.9
-
24.8
3.4
24.8
23.7
19.6
15.5
11.4
-
62
25.2
3.1
25.2
25.2
26.1
21.9
17.6
13.4
22.1
3.3
22.1
22.1
22.1
20.2
16.1
12.0
57
26.0
3.1
26.0
26.0
26.2
22.0
17.7
13.5
23.0
3.3
23.0
23.0
23.0
19.9
15.8
11.7
1200
77
38.7
3.3
25.0
16.7
11.9
-
-
-
34.2
3.6
25.2
15.9
10.5
-
-
-
72
33.9
3.3
27.1
22.3
17.5
12.7
-
-
29.7
3.5
25.2
20.6
15.9
11.3
-
-
67
29.1
3.2
29.1
27.9
23.1
18.3
13.6
-
25.2
3.4
25.2
25.2
21.3
16.6
12.0
-
62
25.7
3.1
25.7
25.7
28.3
23.5
18.8
14.0
22.4
3.3
22.4
22.4
22.4
21.8
17.1
12.5
57
26.5
3.1
26.5
26.5
28.4
23.6
18.9
14.1
23.4
3.3
23.4
23.4
23.4
21.5
16.8
12.2
1350
72
34.2
3.3
29.8
24.4
19.1
13.7
-
-
29.9
3.6
27.9
22.7
17.4
12.2
-
-
67
29.4
3.2
29.4
28.8
25.2
19.8
14.4
-
25.4
3.5
25.4
25.4
23.3
18.1
12.9
-
62
25.9
3.1
25.9
25.9
27.2
21.9
16.5
11.2
22.5
3.3
22.5
22.5
22.5
19.3
14.1
8.9
57
26.7
3.1
26.7
26.7
27.7
22.3
17.0
11.6
23.5
3.4
23.5
23.5
23.5
19.7
14.4
9.2
1500
72
34.5
3.3
32.5
26.5
20.6
14.7
-
-
30.1
3.6
30.1
24.8
19.0
13.2
-
-
67
29.7
3.2
29.7
29.7
27.2
21.2
15.3
-
25.5
3.5
25.5
25.5
25.4
19.6
13.8
-
62
26.2
3.2
26.2
26.2
26.2
20.2
14.3
8.3
22.7
3.4
22.7
22.7
22.7
16.9
11.1
5.3
57
26.9
3.2
26.9
26.9
26.9
21.0
15.1
9.1
23.7
3.4
23.7
23.7
23.7
17.9
12.1
6.3
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower 
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZH037 (3.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65